YASKAWA CIMR-F7A Instruction Manual page 318

Varispeed f7 general purpose inverter
Hide thumbs Also See for CIMR-F7A:
Table of Contents

Advertisement

Con-
Name
stant
Number
Sets motor mechanical loss as a
percentage of motor rated output
(W).
Usually setting is not necessary.
Adjust in the following circum-
Motor
stances:
E2-09
mechanical
• When torque loss is large due
loss
to motor bearing.
• When the torque loss in the
pump or fan is large.
The set mechanical loss will
compensate for torque.
Motor iron
loss for
E2-10
Sets motor iron loss in W units.
torque com-
pensation
Set the rated output of the motor
Motor rated
in units of 0.01 kW.
E2-11
output
This constant is automatically
set during autotuning.
* 1. The factory settings depend on the Inverter capacity. The values for a 200 V Class Inverter of 0.4 kW are given.
* 2. The setting range is 10% to 200% of the Inverter's rated output current. The value for a 200 V Class Inverter of 0.4 kW is given.
For the motor no-load current, set E2-03 to a value less than that of E2-01.
* 3. The setting range depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given. The upper limit depends on the setting of
E2-01.
* 4. The lower limit of E2-08 is the setting value of E2-07.
Manual Motor Constant Setting Methods
The motor constants settings methods are given below. Make (enter) settings referring to the motor test report.
Motor Rated Voltage Setting
Set E2-01 to the rated current on the motor nameplate.
Motor Rated Slip Setting
Set E2-02 to the motor rated slip calculated from the number of rated rotations on the motor nameplate.
Amount of motor rated slip = Motor rated frequency (Hz) - No. of rated rotations (min
poles/120.
Motor No-Load Current Setting
Set E2-03 to the motor no-load current using the rated voltage and rated frequency. The motor no-load current
is not normally written on the motor nameplate. Consult the motor manufacturer.
Factory setting is the no-load current value for a standard Yaskawa 4-pole motor.
Number of Motor Poles Setting
E2-04 is displayed only when V/f control method with PG
number of motor poles (number of poles) as written on the motor nameplate.
Motor Line-to-Line Resistance Setting
E2-05 is set automatically when performing motor line-to-line resistance autotuning. When you cannot per-
form tuning, consult the motor manufacturer for the line-to-line resistance value. Calculate the resistance from
the line-to-line resistance value in the motor test report using the following formula, and then make the setting
accordingly.
Setting
Description
Range
0.0 to
10.0
0 to
65535
0.00 to
650.00
Control Methods
Change
Open
Factory
during
V/f
Loop
Setting
Opera-
V/f
with
Vec-
tion
PG
0.0
No
No
No
14 W
No
A
A
*1
0.40 kW
No
Q
Q
*1
or flux vector control method
Individual Functions
MEMO
BUS
Flux
Regis-
Vec-
ter
tor
tor
No
A
316H
No
No
317H
Q
Q
318H
−1
) x No. of motor
is selected. Set the
121
6-