Detecting Motor Torque

If an excessive load is placed on the machinery (overtorque) or the load is suddenly lightened (undertorque),
you can output an alarm signal to multi-function output terminal M1-M2, P1-PC, P2-PC, P3-C3, or P4-C4.
To use the overtorque/undertorque detection function, set B, 17, 18, 19 (overtorque/undertorque detection NO/
NC) in one of the following constants: H2-01 to H2-05 (multi-function output terminals M1-M2, P1-PC, P2-
PC, P3-C3, and P4-C4 function selection).
The overtorque/undertorque detection level is the current level (Inverter rated output current 100%) in V/f
control, and the motor torque (motor rated torque 100%) in vector control.
Related Constants
Name
Con-
stant
Display
Number
Torque detec-
0: Overtorque/undertorque
tion selection 1
1: Overtorque detection only
2: Overtorque detected
3: Overtorque detection only
4: Overtorque detected
L6-01
Torq Det 1 Sel
5: Undertorque detection only
6: Undertorque detected
7: Undertorque detection only
8: Undertorque detected
Torque detec-
Open-loop vector control: Motor
tion level 1
rated torque is set as 100%.
L6-02
V/f control: Inverter rated current
Torq Det 1 Lvl
is set as 100%.
Setting
Description
Range
detection disabled.
with speed agreement;
operation continues after
overtorque (warning).
continuously during
operation; operation continues
after overtorque (warning).
with speed agreement; output
stopped upon detection
(protected operation).
continuously during
operation; output stopped
upon detection (protected
0 to 8
operation).
with speed agreement;
operation continues after
overtorque (warning).
continuously during
operation; operation continues
after overtorque (warning).
with speed agreement; output
stopped upon detection
(protected operation).
continuously during
operation; output stopped
upon detection (protected
operation).
0 to
300
Control Methods
Change
Open
Factory
during
V/f
Loop
Setting
Opera-
V/f
with
Vector
tion
PG
1
0
No
A
A
A
150%
No
A
A
A
Machine Protection