Alarm Do Output; Using The Scaling Function (Measuring A Flow Meter) - YOKOGAWA GX60 User Manual

Paperless recorder
Table of Contents

Advertisement

Alarm DO output

Alarms are transmitted via DO output to DO channel 1 of
slot 1. (A DO output module is required.)
Configure the following settings in the alarm settings (see
"Setting Alarms").
1
Tap Output type > Relay.
2
Tap the Output No., and enter 0101.
Path
MENU key > Browse tab > Setting >
Setting menu > DO channel settings > Range
1
Tap First-CH > 0101.
2
Check that Last-CH is 0101.
3
Tap Range Type > Alarm.
4
Tap Save.
IM 04L51B01-02EN
Power Specialties, Inc. | www.powerspecialties.com | (816) 353-6550
On channel 1 of slot 1 (0101), measure the input signal
ranging from 1 to 5 VDC as 0.0 to 100.0 m
1
2
1
2
3
1
4
2
3
4
5
6
Operation complete
7
8
9
10
11
Advanced Operation (Various settings and operation)
Using the Scaling Function
(Measuring a flow meter)
Path
MENU key > Browse tab > Setting >
Setting menu > AI channel settings > Range
Tap First-CH > 0101.
Check that Last-CH is 0101.
Tap Type > GS.
Tap Range > 1-5V.
Tap Calculation > Linear scaling.
Drag the screen up.
Show the setting parameters off the screen at the
bottom.
Tap Decimal place > 1.
Tap Scale Lower, and enter 0.0.
Tap Scale Upper, and enter 100.0.
Tap Unit, and enter m3/h.
Tap Save.
3
/h.
1
2
3
4
5
6
7
8
9
10
11
Operation complete