Recommended actions for PlantWeb alerts

RECOMMENDED_ACTION
The RECOMMENDED_ACTION parameter displays a text string that gives a recommended
course of action based on the type and specific event of the PlantWeb alerts are active.
Table 4-2. RB.RECOMMENDED_ACTION
148
Failed/maint/advise
Alarm type
active event
None
None
NV Writes Deferred
Advisory
Configuration Error
Primary Value
Degraded
Maintenance
Calibration Error
Secondary Value
Degraded
Electronics Failure
HW / SW Incompatible
NV Memory Failure
Failed
Primary Value Failure
Secondary Value
Failure
Sensor Drift Alert or
Hot BU active
Diagnostic
Error
Primary Value
Degraded
Recommended action
text string
No action required
Non-volatile writes have been deferred, leave the
device powered until the advisory goes away
Re-write the Sensor Configuration
Confirm the operating range of the applied sensor
and/or verify the sensor connection and device
environment
Retrim the device
Verify the ambient temperature is within operating
limits
Replace the Device
Verify the Hardware Revision is compatible with the
Software Revision
Reset the device then download the Device
Configuration.
Verify the instrument process is within the Sensor
range and/or confirm sensor configuration and
wiring.
Verify sensor range and/or confirm sensor
configuration and wiring
Confirm the operating range of the supplied sensor
and/or verify the sensor connection and device
environment
Confirm the operating range of the supplied sensor
and/or verify the sensor connection and device
environment