Function Blocks - Emerson Rosemount Reference Manual

Temperature transmitter
Hide thumbs Also See for Rosemount:
Table of Contents

Advertisement

Reference Manual
00809-0100-4021, Rev GC
Status
Device is compliant to NAMUR NE 107, ensuring consistent, reliable and standardized device
diagnosti.c information.
The new standard is designed to improve the way device status and diagnostic information is
communicated to operators and maintenance personnel in order to increase productivity and
reduce costs
If self-diagnostics detect a sensor burnout or a transmitter failure, the status of the
measurement will be updated accordingly. The status may also send the PID output to a safe
value.
F
OUNDATION
Schedule entries
Links
Virtual Communications Relationships (VCR)
Backup Link Active Scheduler (LAS)
The transmitter is classified as a device link master, meaning it can function as a Link Active
Scheduler (LAS) if the current link master device fails or is removed from the segment. The host
or other configuration tool downloads the schedule for the application to the link master device.
In the absence of a primary link master, the transmitter will claim the LAS and provide
permanent control for the H1 segment.

Function blocks

Resource block
Transducer block
LCD display block (when an LCD display is used)
Analog input (AI)
Reference data
fieldbus parameters
Contains physical transmitter information including available memory, manufacture
identification, device type, software tag, and unique identification
PlantWeb
Alerts enable the full power of the PW digital architecture by diagnosing
instrumentation issues, communicating the details, and recommending a solution
Contains the actual temperature measurement data, including Sensor 1, Sensor 2, and
terminal (body) temperature
Includes information about sensor type and configuration, engineering units,
linearization, range, damping, and diagnostics
Configures the local display
Processes the measurement and makes it available on the fieldbus segment
Allows filtering, engineering unit, and alarm changes
Appendix A: Reference Data
25 (max.)
30 (max.)
20 (max.)
April 2014
201

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

3144p

Table of Contents