Download Print this page
Emerson Rosemount 3144P Quick Start Manual
Emerson Rosemount 3144P Quick Start Manual

Emerson Rosemount 3144P Quick Start Manual

Temperature transmitters
Hide thumbs Also See for Rosemount 3144P:

Advertisement

Quick Links

Quick Start Guide
00825-0100-4834, Rev FC
January 2024
Rosemount
3144P Temperature
Transmitters
with F
Fieldbus Protocol
OUNDATION

Advertisement

loading

Summary of Contents for Emerson Rosemount 3144P

  • Page 1 Quick Start Guide 00825-0100-4834, Rev FC January 2024 Rosemount 3144P Temperature ™ Transmitters with F Fieldbus Protocol ™ OUNDATION...
  • Page 2: Table Of Contents

    Quick Start Guide January 2024 Contents About this guide........................... 3 Mount the transmitter.........................5 Wire and apply power......................... 7 Verify tagging..........................12 Product certifications........................ 17 Rosemount 3144P...
  • Page 3: About This Guide

    3144P Transmitter. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 3144P Transmitter Reference Manual more instructions. The manual and this guide are also available electronically on Emerson.com/Rosemount.
  • Page 4 Physical security is an important part of any security program and fundamental in protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility. Rosemount 3144P...
  • Page 5: Mount The Transmitter

    January 2024 Quick Start Guide 2  Mount the transmitter Mount the transmitter at a high point in the conduit run to prevent moisture from draining into the transmitter housing. 2.1  Typical North American installation Procedure 1. Mount the thermowell to the process container wall. 2.
  • Page 6 9. Insert shielded cable leads through the cable entries into the connection head/transmitter. Connect and tighten cable glands. 10. Connect the shielded cable leads to the connection head terminals (located inside the connection head) and to the sensor wiring terminals (located inside the transmitter housing). Rosemount 3144P...
  • Page 7: Wire And Apply Power

    RTD with a compensation loop. Table 3-2: Dual sensor Emerson provides four-wire sensors for all single-element RTDs. To use these RTDs in three-wire configurations, leave the unneeded leads disconnected and insulated with electrical tape This table refers to wiring dual sensors for ΔT and Hot Backup ™...
  • Page 8 Enclosure covers must be fully engaged to meet explosion- proof requirements. 5. Apply power. 3.3  Ground the transmitter 3.3.1  Ungrounded thermocouple, mV, and RTD/ohm inputs Each process installation has different requirements for grounding. Use the grounding options recommended by the facility for the Rosemount 3144P...
  • Page 9 Quick Start Guide specific sensor type or begin with grounding option 1 (the most common). Ground the transmitter: option 1 Emerson recommends this option for ungrounded transmitter housing. Procedure 1. Connect signal wiring shield to the sensor wiring shield. 2. Ensure the two shields are tied together and electrically isolated from the transmitter housing.
  • Page 10 3. Ground signal wiring shield at the power supply end. A. Sensor wire B. Transmitter C. Shield ground point 3.3.2  Ground thermocouple inputs Procedure 1. Ground sensor wiring shield at the sensor. Rosemount 3144P...
  • Page 11 January 2024 Quick Start Guide 2. Ensure the sensor wiring and signal wiring shields are electrically isolated from the transmitter housing and other grounded fixtures. 3. Ground signal wiring shield at the power supply end. A. Sensor wire B. Transmitter C. Shield ground point Quick Start Guide...
  • Page 12: Verify Tagging

    Note The device description loaded in the host system must be at the same revision as this device. You can download the device description from Emerson.com/Rosemount. 4.1.1  Verify transmitter configuration Each F Fieldbus host or configuration tool has a different OUNDATION way of displaying and performing configurations.
  • Page 13 Quick Start Guide The following is the minimum configuration requirement for a temperature measurement. This guide is designed for systems not using DD methods. For a complete list of parameters and configuration information, refer to the Rosemount 3144P Temperature Transmitter Reference Manual.
  • Page 14 XD_SCALE Set desired measurement range and units. Units must be one of the following: • • Ohms • °C • °F • °R • OUT_SCALE For “DIRECT” L_TYPE, set OUT_SCALE to match XD_SCALE Rosemount 3144P...
  • Page 15 January 2024 Quick Start Guide (continued) Table 4-2: AI Block Parameters Parameter Comments HI_HI_LIM Process alarms. HI_LIM Must be within the range defined by “OUT_SCALE” LO_LIM LO_LO_LIM Note To make changes to the AI block, set the BLOCK_MODE (TARGET) to OOS (out of service). After making the changes, return the BLOCK_MODE TARGET to AUTO.
  • Page 16 Quick Start Guide January 2024 5. Apply power and set the loop to automatic control. Rosemount 3144P...
  • Page 17: Product Certifications

    European Directive information A copy of the EU Declaration of Conformity can be found at the end of this guide The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount. 5.2  Ordinary location certification As standard, the device has been examined and tested to determine...
  • Page 18 2. Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that cause electrostatic build-up on painted surfaces and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information. Rosemount 3144P...
  • Page 19 January 2024 Quick Start Guide 3. See instructions for relation between process temperature, ambient temperature, and temperature class/ maximum surface temperature "T". 4. For 3144P temperature transmitters with "XA" designation, the spring-loaded adapter style sensors must be installed in a thermowell to maintain Ex tb protection. Process temperature Ambient temperature Temperature class...
  • Page 20 -60 °C to +80 °C -60 °C to +80 °C T130 °C Sensor connection is where the sensor threads into the transmitter or junction box housing 5.5  International 5.5.1  E7 IECEx Flameproof IECEx DEK 19.0041X Certificate IEC 60079-0:2017, IEC 60079-1:2014-06 Standards Rosemount 3144P...
  • Page 21 January 2024 Quick Start Guide Ex db IIC T6…T1 Gb, T6(-60 °C ≤ T ≤ +70 °C), T5…T1(-60 Markings °C ≤ T ≤ +80 °C) Specific Conditions of Use (X): 1. Flameproof joints are not intended for repair. 2. Non-Standard paint options may cause risk from electrostatic discharge.
  • Page 22 ≤ +75 °C); Ex ec IIC T5 Gc; Markings T5 (-40°C ≤ Ta ≤ +75°C) Special Condition for Safe Use (X): When fitted with the transient terminal options, the apparatus is not capable of withstanding the 500V electrical strength test as defined in Rosemount 3144P...
  • Page 23 January 2024 Quick Start Guide Clause 6.5.1 of IEC 60079-15: 2010 or Clause 6.1 of IEC 60079-7:2017. This must be taken into account during installation. 5.6  Brazil 5.6.1  E2 INMETRO Flameproof and Dust UL-BR 21.1296X Certificate ABNT NBR IEC 60079-0:2020; ABNT NBR IEC Standards 60079-1:2016;...
  • Page 24 -60 °C ≤ T ≤ +80 °C -60 °C ≤ T ≤ +80 °C T130 °C • 产品使用注意事项 1. 产品外壳设有接地端子,用户在使用时应可靠接地。 2. 安装现场应不存在对产品外壳有腐蚀作用的有害气体。 3. 现场安装时,电缆引入口须选用国家指定的防爆检验机构按检 验认可、具有 Ex db IIC Gb 、 Ex tb IIIC Db 防爆等级的电 缆引入装置或堵封件,冗余电缆引入口须用堵封件有效密封。 4. 用于爆炸性气体环境中,现场安装、使用和维护必须严格遵守 “断电后开盖!”的警告语。用于爆炸性粉尘环境中,现场安装、 Rosemount 3144P...
  • Page 25 January 2024 Quick Start Guide 使用和维护必须严格遵守“爆炸性粉尘场所严禁开盖!”的警告 语。 5. 用于爆炸性粉尘环境中,产品外壳表面需保持清洁,以防粉尘 堆积,但严禁用压缩空气吹扫。 6. 用户不得自行更换该产品的零部件,应会同产品制造商共同解 决运行中出现的故障,以杜绝损坏现象的发生。 7. 产品的安装、使用和维护应同时遵守产品使用说明书、GB/T 3836.13-2021“爆炸性环境 第 13 部分:设备的修理、检修、修 复和改造”、GB/ T3836.15-2017“爆炸性环境 第 15 部分:电 气装置的设计、选型和安装”、GB/ T3836.16-2017“爆炸性环 境 第 16 部分:电气装置的检查与维护”、GB50257-2014“电气 装置安装工程爆炸和火灾危险环境电力装置施工及验收规范” 和 GB15577-2018"粉尘防爆安全规程"的有关规定。 5.7.2  I3 China Intrinsic Safety GYJ21.1278X Certificate GB/T3836.1-2021, GB/T 3836.4-2021 Standards Ex ia IIC T4 Ga Markings...
  • Page 26 5.7.3  N3 China Type n GYJ20.1086X Certificate GB/T 3836.1-2021, GB/T 3836.3-2021 Standards Ex ec IIC T5 Gc Markings Output T code Ambient temperature Fieldbus -40 °C ≤ T ≤ +75 °C • 产品安全使用特殊条件 产品防爆合格证后缀“X”代表产品安全使用有特殊条件: 此设备不能承受 500V 交流有效值介电强度试验,安装时需考虑在内。 • 产品使用注意事项 Rosemount 3144P...
  • Page 27 January 2024 Quick Start Guide Fieldbus: -40 °C ≤ T ≤ +75 °C 1. 输入参数: = 32 Vdc = 2.1 nF (Loop terminals) = 7.7 nF (Sensor terminals) 2. 产品外壳设有接地端子,用户在安装使用时应可靠接地。 3. 产品外壳防护等级(IP 代码)为 IP54。 4. 现场安装时,电缆引入口须选用国家指定的防爆检验机构按检验认 可、符合 GB/T 3836.1-2021、GB/T 3836.3-2021 要求且具有 Ex ec IIC 防爆等级、达到...
  • Page 28 If paint is ordered through a special option code, contact the manufacturer for more information. 3. See instructions for relation between process temperature, ambient temperature and temperature class. Rosemount 3144P...
  • Page 29 January 2024 Quick Start Guide Process temperature Ambient temperature Temperature class range at sensor range (°C) connection (°C) -60 °C to +70 °C -60 °C to +70 °C -60 °C to +80 °C -60 °C to +80 °C T5...T1 Sensor Connection is where the sensor threads into the transmitter or junction box housing.
  • Page 30 SDN Det Norske Veritas (DNV) type approval TAA00001JK Certificate Det Norske Veritas’ rules for classification of ships, Intended use high speed, and light craft and Det Norske Veritas' offshore standards Application Table 5-5: Location classes Temperature Humidity Vibration Enclosure Rosemount 3144P...
  • Page 31 January 2024 Quick Start Guide 5.13  Installation drawings for intrinsic safety Quick Start Guide...
  • Page 32 Quick Start Guide January 2024 Rosemount 3144P...
  • Page 33 January 2024 Quick Start Guide Quick Start Guide...
  • Page 34 Quick Start Guide January 2024 5.14  Declaration of conformity Rosemount 3144P...
  • Page 35 January 2024 Quick Start Guide Quick Start Guide...
  • Page 36 Quick Start Guide January 2024 Rosemount 3144P...
  • Page 37 January 2024 Quick Start Guide 5.15  China RoHS Quick Start Guide...
  • Page 38 Quick Start Guide January 2024 Rosemount 3144P...
  • Page 39 January 2024 Quick Start Guide Quick Start Guide...
  • Page 40 2024 Emerson. All rights reserved. Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners.