Quick Start Guide January 2024 Contents About this guide........................... 3 Mount the transmitter.........................5 Wire and apply power......................... 7 Verify tagging..........................12 Product certifications........................ 17 Rosemount 3144P...
3144P Transmitter. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 3144P Transmitter Reference Manual more instructions. The manual and this guide are also available electronically on Emerson.com/Rosemount.
Page 4
Physical security is an important part of any security program and fundamental in protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility. Rosemount 3144P...
January 2024 Quick Start Guide 2 Mount the transmitter Mount the transmitter at a high point in the conduit run to prevent moisture from draining into the transmitter housing. 2.1 Typical North American installation Procedure 1. Mount the thermowell to the process container wall. 2.
Page 6
9. Insert shielded cable leads through the cable entries into the connection head/transmitter. Connect and tighten cable glands. 10. Connect the shielded cable leads to the connection head terminals (located inside the connection head) and to the sensor wiring terminals (located inside the transmitter housing). Rosemount 3144P...
RTD with a compensation loop. Table 3-2: Dual sensor Emerson provides four-wire sensors for all single-element RTDs. To use these RTDs in three-wire configurations, leave the unneeded leads disconnected and insulated with electrical tape This table refers to wiring dual sensors for ΔT and Hot Backup ™...
Page 8
Enclosure covers must be fully engaged to meet explosion- proof requirements. 5. Apply power. 3.3 Ground the transmitter 3.3.1 Ungrounded thermocouple, mV, and RTD/ohm inputs Each process installation has different requirements for grounding. Use the grounding options recommended by the facility for the Rosemount 3144P...
Page 9
Quick Start Guide specific sensor type or begin with grounding option 1 (the most common). Ground the transmitter: option 1 Emerson recommends this option for ungrounded transmitter housing. Procedure 1. Connect signal wiring shield to the sensor wiring shield. 2. Ensure the two shields are tied together and electrically isolated from the transmitter housing.
Page 10
3. Ground signal wiring shield at the power supply end. A. Sensor wire B. Transmitter C. Shield ground point 3.3.2 Ground thermocouple inputs Procedure 1. Ground sensor wiring shield at the sensor. Rosemount 3144P...
Page 11
January 2024 Quick Start Guide 2. Ensure the sensor wiring and signal wiring shields are electrically isolated from the transmitter housing and other grounded fixtures. 3. Ground signal wiring shield at the power supply end. A. Sensor wire B. Transmitter C. Shield ground point Quick Start Guide...
Note The device description loaded in the host system must be at the same revision as this device. You can download the device description from Emerson.com/Rosemount. 4.1.1 Verify transmitter configuration Each F Fieldbus host or configuration tool has a different OUNDATION way of displaying and performing configurations.
Page 13
Quick Start Guide The following is the minimum configuration requirement for a temperature measurement. This guide is designed for systems not using DD methods. For a complete list of parameters and configuration information, refer to the Rosemount 3144P Temperature Transmitter Reference Manual.
Page 14
XD_SCALE Set desired measurement range and units. Units must be one of the following: • • Ohms • °C • °F • °R • OUT_SCALE For “DIRECT” L_TYPE, set OUT_SCALE to match XD_SCALE Rosemount 3144P...
Page 15
January 2024 Quick Start Guide (continued) Table 4-2: AI Block Parameters Parameter Comments HI_HI_LIM Process alarms. HI_LIM Must be within the range defined by “OUT_SCALE” LO_LIM LO_LO_LIM Note To make changes to the AI block, set the BLOCK_MODE (TARGET) to OOS (out of service). After making the changes, return the BLOCK_MODE TARGET to AUTO.
Page 16
Quick Start Guide January 2024 5. Apply power and set the loop to automatic control. Rosemount 3144P...
European Directive information A copy of the EU Declaration of Conformity can be found at the end of this guide The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount. 5.2 Ordinary location certification As standard, the device has been examined and tested to determine...
Page 18
2. Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that cause electrostatic build-up on painted surfaces and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information. Rosemount 3144P...
Page 19
January 2024 Quick Start Guide 3. See instructions for relation between process temperature, ambient temperature, and temperature class/ maximum surface temperature "T". 4. For 3144P temperature transmitters with "XA" designation, the spring-loaded adapter style sensors must be installed in a thermowell to maintain Ex tb protection. Process temperature Ambient temperature Temperature class...
Page 20
-60 °C to +80 °C -60 °C to +80 °C T130 °C Sensor connection is where the sensor threads into the transmitter or junction box housing 5.5 International 5.5.1 E7 IECEx Flameproof IECEx DEK 19.0041X Certificate IEC 60079-0:2017, IEC 60079-1:2014-06 Standards Rosemount 3144P...
Page 21
January 2024 Quick Start Guide Ex db IIC T6…T1 Gb, T6(-60 °C ≤ T ≤ +70 °C), T5…T1(-60 Markings °C ≤ T ≤ +80 °C) Specific Conditions of Use (X): 1. Flameproof joints are not intended for repair. 2. Non-Standard paint options may cause risk from electrostatic discharge.
Page 22
≤ +75 °C); Ex ec IIC T5 Gc; Markings T5 (-40°C ≤ Ta ≤ +75°C) Special Condition for Safe Use (X): When fitted with the transient terminal options, the apparatus is not capable of withstanding the 500V electrical strength test as defined in Rosemount 3144P...
Page 23
January 2024 Quick Start Guide Clause 6.5.1 of IEC 60079-15: 2010 or Clause 6.1 of IEC 60079-7:2017. This must be taken into account during installation. 5.6 Brazil 5.6.1 E2 INMETRO Flameproof and Dust UL-BR 21.1296X Certificate ABNT NBR IEC 60079-0:2020; ABNT NBR IEC Standards 60079-1:2016;...
Page 24
-60 °C ≤ T ≤ +80 °C -60 °C ≤ T ≤ +80 °C T130 °C • 产品使用注意事项 1. 产品外壳设有接地端子,用户在使用时应可靠接地。 2. 安装现场应不存在对产品外壳有腐蚀作用的有害气体。 3. 现场安装时,电缆引入口须选用国家指定的防爆检验机构按检 验认可、具有 Ex db IIC Gb 、 Ex tb IIIC Db 防爆等级的电 缆引入装置或堵封件,冗余电缆引入口须用堵封件有效密封。 4. 用于爆炸性气体环境中,现场安装、使用和维护必须严格遵守 “断电后开盖!”的警告语。用于爆炸性粉尘环境中,现场安装、 Rosemount 3144P...
Page 26
5.7.3 N3 China Type n GYJ20.1086X Certificate GB/T 3836.1-2021, GB/T 3836.3-2021 Standards Ex ec IIC T5 Gc Markings Output T code Ambient temperature Fieldbus -40 °C ≤ T ≤ +75 °C • 产品安全使用特殊条件 产品防爆合格证后缀“X”代表产品安全使用有特殊条件: 此设备不能承受 500V 交流有效值介电强度试验,安装时需考虑在内。 • 产品使用注意事项 Rosemount 3144P...
Page 27
January 2024 Quick Start Guide Fieldbus: -40 °C ≤ T ≤ +75 °C 1. 输入参数: = 32 Vdc = 2.1 nF (Loop terminals) = 7.7 nF (Sensor terminals) 2. 产品外壳设有接地端子,用户在安装使用时应可靠接地。 3. 产品外壳防护等级(IP 代码)为 IP54。 4. 现场安装时,电缆引入口须选用国家指定的防爆检验机构按检验认 可、符合 GB/T 3836.1-2021、GB/T 3836.3-2021 要求且具有 Ex ec IIC 防爆等级、达到...
Page 28
If paint is ordered through a special option code, contact the manufacturer for more information. 3. See instructions for relation between process temperature, ambient temperature and temperature class. Rosemount 3144P...
Page 29
January 2024 Quick Start Guide Process temperature Ambient temperature Temperature class range at sensor range (°C) connection (°C) -60 °C to +70 °C -60 °C to +70 °C -60 °C to +80 °C -60 °C to +80 °C T5...T1 Sensor Connection is where the sensor threads into the transmitter or junction box housing.
Page 30
SDN Det Norske Veritas (DNV) type approval TAA00001JK Certificate Det Norske Veritas’ rules for classification of ships, Intended use high speed, and light craft and Det Norske Veritas' offshore standards Application Table 5-5: Location classes Temperature Humidity Vibration Enclosure Rosemount 3144P...
Page 31
January 2024 Quick Start Guide 5.13 Installation drawings for intrinsic safety Quick Start Guide...
Page 32
Quick Start Guide January 2024 Rosemount 3144P...
Page 33
January 2024 Quick Start Guide Quick Start Guide...
Page 34
Quick Start Guide January 2024 5.14 Declaration of conformity Rosemount 3144P...
Page 35
January 2024 Quick Start Guide Quick Start Guide...
Page 36
Quick Start Guide January 2024 Rosemount 3144P...
Page 37
January 2024 Quick Start Guide 5.15 China RoHS Quick Start Guide...
Page 38
Quick Start Guide January 2024 Rosemount 3144P...
Page 39
January 2024 Quick Start Guide Quick Start Guide...
Page 40
2024 Emerson. All rights reserved. Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners.