Reference Manual
00809-0100-4021, Rev GC
5.
6.
7.
8.
HART® commissioning
When prompted, choose the sensor type. This must be Cal VanDusen for this option.
Press Enter.
This will reset any Min/Max values tracking this sensor and any Min/Max values tracking
Differential, Average, or First Good. Press OK.
It will now display the current Callendar-Van Dusen coefficients for the sensor (Alpha,
beta, Delta, R0, A, B, C). Press OK.
Select which set of CVD coefficients you would like to enter for that sensor. Choose
between 1 R0, A, B, C, and 2 R0, Alpha, Beta, Delta.
Section 3: HART commissioning
April 2014
127