Product Specification Sheet 00815-0100-4810, Rev AA June 2005 Conditioning Orifice Plate Specification Guide www.rosemount.com...
Page 2
Overview This Product Specification sheet defines the requirements for the Conditioning Orifice Plate (COP). This Specification is also included for Electronic Pressure Instruments when integrated with the Conditioning Orifice Plate (COP) primary to form complete flowmeters. Vendor Requirements The manufacturer of the COP shall be certified to the international standard ISO 9001.
Page 3
Product Specification Sheet 00815-0100-4810, Rev AA June 2005 Functional Specifications • The pressure instrument shall have the capability to be supplied as mounted directly on the COP primary when the process temperature is less than 450°F (232°C). • Differential pressure instruments shall be capacitance technology-based.
Page 4
HART protocol. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. HART is a registered trademark of the HART Communications Foundation. OUNDATION fieldbus is a registered trademark of the Fieldbus Foundation.