Note
Enabling Drift Alert Option Warning only will set a flag (through HART) whenever the maximum
acceptable difference between Sensor 1 and Sensor 2 has been exceeded. For the transmitter's
analog signal to go into alarm when Drift Alert is detected, select Alarm in
Configure Sensor Drift in guided setup
Enable Sensor Drift Alert in guided setup: Fast Keys 2-1-6
1.
2.
3.
4.
5.
HART® commissioning
From the Home Screen, select 2 Configure.
Select 1 Guided Setup.
Select 6 Config Drift Alert.
Select 1 Enable to activate Sensor Drift Alert and press ENTER.
When prompted, select whether you want Sensor Drift Alert to put the transmitter into
"Alarm" or "Warning", and press ENTER. Enabling Drift Alert Option Warning only will
set a flag (through HART) whenever the maximum acceptable difference between
Sensor 1 and Sensor 2 has been exceeded. Enabling Drift Alert Option Alarm will send
the transmitter's analog signal into alarm when Drift Alert is detected.
Section 3: HART commissioning
Alarm switch (HART)
April 2014
.
81