Quick Start Guide
00825-0100-4021, Rev LB
July 2017
Rosemount
3144P Temperature
Transmitter
®
with HART
Protocol and Rosemount X-well
Technology

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Rosemount 3144P and is the answer not in the manual?

Questions and answers

Summary of Contents for Emerson Rosemount 3144P

  • Page 1 Quick Start Guide 00825-0100-4021, Rev LB July 2017 ™ Rosemount 3144P Temperature Transmitter ® ™ with HART Protocol and Rosemount X-well Technology...
  • Page 2: Table Of Contents

    July 2017 Quick Start Guide NOTICE This guide provides basic guidelines for the Rosemount 3144P Transmitter. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 3144P Transmitter...
  • Page 3: System Readiness

    Rosemount X-well Technology functionality.The Device Descriptors are available with new communicators at Emerson.com/Rosemount or can be loaded into existing communicators at any Emerson Service Center. The device descriptors are as follows: Device in HART 5 mode: Device v5 DD v1 Device in HART 7 mode: Device v7 DD v1 Perform the following steps to determine if an upgrade is required.
  • Page 4 Switch HART revision mode If the HART configuration tool is not capable of communicating with HART Revision 7, the Rosemount 3144P Transmitter will load a generic menu with limited capability. The following procedures will switch the HART revision mode from the generic menu: 1.
  • Page 5 Quick Start Guide July 2017 Function HART 5 Fast Keys HART 7 Fast Keys Average Temperature Setup 2, 2, 3, 3 2, 2, 3, 3 Burst Mode 2, 2, 8, 4 Comm Status 1, 2 Configure additional messages 2, 2, 8, 4, 7 Configure Hot Backup 2, 2, 4, 1, 3 2, 2, 4, 1, 3...
  • Page 6: Set The Switches

    2, 2, 1, 11 Set the switches Configure alarms and lock device The Rosemount 3144P Transmitter comes with hardware switches to configure alarms and lock the device. Use the following procedure to set the switches: Without a LCD display 1. Set the loop to manual (if applicable) and disconnect the power.
  • Page 7: July

    Quick Start Guide July 2017 5. Screw the sensor into the thermowell or directly into the process (depending on installation requirements). 6. Verify all sealing requirements. 7. Attach the transmitter to the thermowell/sensor assembly. Seal all threads with an approved thread sealant, such as silicone or PTFE tape (if required). 8.
  • Page 8 July 2017 Quick Start Guide 10.Connect the shielded cable leads to the connection head terminals (located inside the connection head) and to the sensor wiring terminals (located inside the transmitter housing). A. Cable gland B. Shielded cable from sensor to transmitter C.
  • Page 9: Wire And Apply Power

    5. Although it will come factory configured as such, ensure that pipe clamp RTD sensor is assembled in 4-wire configuration. Figure 2. Rosemount 3144P Transmitter with Rosemount X-well Technology Installation Drawing Wire and apply power Wire the transmitter Wiring diagrams are located inside the terminal block cover.
  • Page 10 July 2017 Quick Start Guide Figure 4. Rosemount 3144P Dual-Sensor ΔT/Hot ΔT/Hot ΔT/Hot ΔT/Hot ΔT/Hot Backup/Dual Backup/Dual Backup/Dual Backup/Dual Backup/Dual Sensor with two Sensor with two Sensor with two Sensor with RTDs/ Sensor with RTDs/ RTDs with RTDs Thermocouples Thermocouples...
  • Page 11: Ground The Transmitter

    Quick Start Guide July 2017 Figure 5. Load Limitation Maximum load = 40.8 3 (Supply voltage - 12.0) 4−20 mA dc 1240 1100 1000 42.4 18.1 12.0 Min A. HART and analog operating range B. Analog only operating range 1. Without transient protection (optional). Ground the transmitter Ungrounded thermocouple, mV, and RTD/ohm Inputs Each process installation has different requirements for grounding.
  • Page 12 July 2017 Quick Start Guide Option 2 (recommended for grounded transmitter housing) 1. Connect sensor wiring shield to the transmitter housing (only if the housing is grounded). 2. Ensure the sensor shield is electrically isolated from surrounding fixtures that may be grounded. 3.
  • Page 13: Perform A Loop Test

    2. The transmitter will output the alarm current level based on the configured alarm parameter and switch settings. 3. Select 5 End to return the transmitter to normal conditions. Safety Instrumented System (SIS) For safety certified installations, refer to the Rosemount 3144P Reference Manual The manual is available electronically on Emerson.com/Rosemount...
  • Page 14: Product Certifications

    A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount. Ordinary Location Certification As standard, the transmitter has been examined and tested to determine that...
  • Page 15 Quick Start Guide July 2017 K6 CSA Explosionproof, Intrinsic Safety and Division 2 Certificate: 1242650 Standards: CAN/CSA C22.2 No. 0-M91 (R2001), CSA Std C22.2 No. 30-M1986; CAN/CSA-C22.2 No. 94-M91, CSA Std C22.2 No. 142-M1987, CAN/CSA-C22.2 No. 157-92, CSA Std C22.2 No. 213-M1987 Markings: Explosionproof for Class I, Groups A, B, C, D;...
  • Page 16 July 2017 Quick Start Guide N1 ATEX Type n Certificate: BAS01ATEX3432X [HART]; Baseefa03ATEX0709X [Fieldbus] Standards: EN 60079-0:2012, EN 60079-15:2010 II 3 G Ex nA IIC T5/T6 Gc; T6(-40 °C ≤ T ≤ +50 °C), Markings: HART: T5(-40 °C ≤ T ≤...
  • Page 17 Quick Start Guide July 2017 7. Non-Standard Paint options may cause risk from electrostatic discharge. Avoid installations that cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
  • Page 18 July 2017 Quick Start Guide 2. The enclosure may be made from aluminum alloy with a protective polyurethane paint finish; however, care should be taken to protect it from impact and abrasion when located in areas that require EPL Ga (Zone 0). INMETRO Intrinsic Safety [Fieldbus/FISCO] Certificate: UL-BR 15.0030X Standards: ABNT NBR IEC 60079-0:2008 + Errata 1:2011, ABNT NBR IEC 60079-11:2009...
  • Page 19 Quick Start Guide July 2017 China Intrinsic Safety Certificate: GYJ16.1338X Standards: GB3836.1-2010, GB3836.4-2010, GB3836.20-2010 Markings: Ex ia IIC T4/T5/T6 Special Conditions for Safe Use (X): 1. Symbol “X” is used to denote specific conditions of use: a. The enclosure may contain light metal, attention should be taken to avoid ignition hazard due to impact or friction when used in Zone 0.
  • Page 20 July 2017 Quick Start Guide Temperature transmitters comply to the requirements for FISCO field devices specified in GB3836.19-2010. FISCO parameters are as follows: Maximum internal Maximum input Maximum input Maximum input parameters voltage: U current: l (mA) power: P (nF) (μH) 17.5 5.32...
  • Page 21 Quick Start Guide July 2017 EAC - Belarus, Kazakhstan, Russia EM Technical Regulation Customs Union (EAC) Flameproof Certificate: RU C-US.GB05.B.00289 Markings: 1Ex d IIC T6…T1 Gb X Special Condition for Safe Use (X): 1. See certificate for special conditions. Technical Regulation Customs Union (EAC) Intrinsic Safety Certificate: RU C-US.GB05.B.00289 ®...
  • Page 22 Certificate: 23154 Requirements: Bureau Veritas Rules for the Classification of Steel Ships Application: Class notations: AUT-UMS, AUT-CCS, AUT-PORT and AUT-IMS; Temperature transmitter type Rosemount 3144P cannot be installed on diesel engines SDN Det Norske Veritas (DNV) Type Approval Certificate: A-14184 Intended Use: Det Norske Veritas’...
  • Page 23 Quick Start Guide July 2017 Application: Location classes Temperature Humidity Vibration Enclosure SLL Lloyds Register (LR) Type Approval Certificate: 11/60002 Application: Environmental categories ENV1, ENV2, ENV3, and ENV5...
  • Page 24: Eu Declaration Of Conformity

    July 2017 Quick Start Guide Figure 6. Rosemount 3144P Declaration of Conformity EU Declaration of Conformity No: RMD 1045 Rev. J Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 declare under our sole responsibility that the product, Rosemount 3144P Temperature Transmitter manufactured by, Rosemount, Inc.
  • Page 25 No: RMD 1045 Rev. J EMC Directive (2014/30/EU) Harmonized Standards: EN61326-1:2013, EN61326-2-3: 2013 ATEX Directive (2014/34/EU) Rosemount 3144P Temperature Transmitter (4-20mA/HART Output) BAS01ATEX1431X – Intrinsic Safety Certificate Equipment Group II, Category 1 G (Ex ia IIC T5/T6 Ga) Harmonized Standards: EN60079-0:2012, EN60079-11:2012 BAS01ATEX3432X –...
  • Page 26 July 2017 Quick Start Guide EU Declaration of Conformity No: RMD 1045 Rev. J Rosemount 3144P Temperature Transmitter (all Output Protocols) FM12ATEX0065X – Dust Certificate Equipment Group II, Category 2 D (Ex tb IIIC T130°C Db) Harmonized Standards: EN 60079-0:2012+A11:2013, EN 60079-31:2014 FM12ATEX0065X –...
  • Page 27 Quick Start Guide July 2017 China RoHS Rosemount 3144P List of Rosemount 3144P Parts with China RoHS Concentration above MCVs Hazardous Substances Hexavalent Polybrominated Polybrominated Part Name Lead Mercury Cadmium Chromium biphenyls diphenyl ethers (Pb) (Hg) (Cd) (Cr +6) (PBB)
  • Page 28 Terms +65 6777 0947 and Conditions of Sale page. Enquiries@AP.Emerson.com The Emerson logo is a trademark and service mark of Emerson Electric Co. Middle East and Africa Regional Office Rosemount X-well, Rosemount, and Rosemount logotype are Emerson Automation Solutions trademarks of Emerson.

Table of Contents