HART® commissioning
Select 1 Enable to activate Sensor Drift Alert and press ENTER.
When prompted, select whether you want Sensor Drift Alert to put the transmitter into
"Alarm" or "Warning", and press ENTER. Enabling Drift Alert Option Warning only will
set a flag (through HART) whenever the maximum acceptable difference between
Sensor 1 and Sensor 2 has been exceeded. Enabling Drift Alert Option Alarm will send
the transmitter's analog signal into alarm when Drift Alert is detected.
Select the engineering units you would like to use and press ENTER. Choose from degC,
degF, degR, Kelvin, mV, Ohms.
Enter the Sensor Drift Alert threshold value and press ENTER. This is a digital value that
triggers the Drift Alert feature. When this limit is exceeded, the transmitter will go into
alarm or generate a warning (depending on the alert mode chosen previously).
Section 3: HART commissioning
April 2014