Mod - Mode Inputs Setup; Msl - Magnet Slowing Type; Nr - Door Nudging Setup; Prk - Park/Zone With Doors Open - ECD 100-181 Manual

Table of Contents

Advertisement

E E P R O M S E T T I N G S
L.#...EEPROM...Lift # (VALUE). Set value to lift number. (01 to 06 valid values.)
01: 00000001 (Lift 1)
02: 00000010 (Lift 2)
03: 00000011 (Lift 3)
04: 00000100 (Lift 4)
05: 00000101 (Lift 5)
06: 00000110 (Lift 6)

MOD - MODE Inputs setup

Enables the 3 MODE inputs to be inverted. CFS, HFS, IND
MOD EEPROM (MASK)
08: 00001000 CFS. Car fire service input inverted
20: 00100000 HFS. Hall fire service input inverted
40: 01000000 IND. Independent Operation input inverted
All other inputs default to 0.

MSL - Magnet Slowing type

Sets the slowing/counting type.
00: 00000000 MSU/MSD magnet slowing.
01: 00000001 Pulse slowing.
See also Section 6: Motion – EEprom MSL setting "00" and "01"

NR - Door Nudging setup

Sets the door nudging feature on or off. (Nudging time is preset).
See also output, NRF and NRR
See also output, NDGF and NDGR
Sets "NDGF and NDGR" output on or off to control the floor passing tone.
00: 00000000 No door nudging or passing tone
01: 00000001 Door nudging only
02: 00000010 Door nudging and passing tone
03: 00000011 Passing tone only
04: 00000100 Sets EDP/OS time to 180 secs. See also Input - Output, EDP

PRK - Park/Zone with doors open

This setting sets the lift to Zone with the doors open.
PRK EEPROM value.
00: 00000000 "Normal."
01: 00000001 "PRK doors open."

PRV - Proving required setup

If set to "01" PRV input is required to be on prior to starting a run, irrelevant of DRV type selected.
See also Input - Output, PRV.

RLV - Re-Leveling setup

This sets the floor re-leveling function on/off
Setting example 00: 00000000 off. Lift will NOT re-level.
01: 00000000 on. Lift will re-level.
Note: Lift only re-levels if doors are either fully opened or closed.

Advertisement

Table of Contents
loading

Table of Contents