Re-Leveling Won't Operate; Red3 Led Is Not Blinking; Processor Errors/Lockup - ECD 100-181 Manual

Table of Contents

Advertisement

1. Ensure SIS unit is mounted firmly.
2. Some magnets may have dead spots. Change faulty magnets.
3. Ensure software is latest Version.
4. On terminal floors – ensure that MSU/MSD initiates slowing before TSL/BSL respectively.

Re-leveling won't operate

Check RLV setting.

Red3 LED is not blinking

The microprocessor has locked up (possibility caused by electrical noise interference, power failure). Reset via a processor
power on reset (POR);
Under normal operation;
• The red Red3 LED blinks to confirm that the microprocessor is running.
• The yellow Yel3 LED comes on to confirm outputs are enabled.
• The green Grn3 LED comes on during power up and turns off during normal operation. It will
When re-powering; ensure the lift is off for 10 seconds before turning back on.
On power up, a delay of approximately 2 seconds is given on start up to ensure voltages are stable prior to reading
and writing outputs.

Processor errors/Lockup:

Ensure 0V and 10V AC supply present at board terminal
Try new microprocessor IC.
35V 470uF capacitor damaged.
Crystal damaged.
Lockup may be due to spike/noise. All relays, valves, brakes, door motors etc must be suppressed with an
appropriate filter or surge absorber unit to prevent voltage spikes and back emf/noise.
• Turn the power supply off
• Wait for 10s
• Turn the power supply back on
• Observe LEDs status.
also flash once when a new value has been written in to EEPROM..