Dthf - Door Time Hall Call (Front Doors) Close Setup; Dthr - Door Time Hall Call (Rear Doors) Close Setup; Dtl - Door Time Lobby Call Close Setup; Dtrf - Door Time Recall Front Setup - ECD 100-181 Manual

Table of Contents

Advertisement

E E P R O M S E T T I N G S
32: 00110010 = 5000ms, "5 seconds"
90: 10010000 = 14400ms, "14.4 seconds"
(01 to FF valid values.)

DTHF - Door Time Hall call (Front doors) close setup

Sets the amount of time before the front doors close for a hall call whilst on normal operation.
Lobby time (DTL) overrides this setting when lift is at the lobby floor.
Recommend DTHF is set equal to or greater than DTCF.
DTHF EEPROM Front door hall call time close. (VALUE)
Set value for front door close time.
The time is set in 100ms increments.
1e: 00011110 = 3000ms, "3 seconds"
32: 00110010 = 5000ms, "5 seconds"
90: 10010000 = 14400ms, "14.4 seconds"
(01 to FF valid values.)

DTHR - Door Time Hall call (Rear doors) close setup

Sets the amount of time before the rear doors close for a hall call whilst on normal operation.
Lobby time (DTL) overrides this setting when lift is at the lobby floor.
Recommend DTHR is set equal to or greater than DTCR.
DTHR EEPROM Rear door hall call time close. (VALUE)
Set value for rear door close time.
The time is set in 100ms increments.
1e: 00011110 = 3000ms, "3 seconds"
32: 00110010 = 5000ms, "5 seconds"
90: 10010000 = 14400ms, "14.4 seconds"
(01 to FF valid values.)

DTL - Door Time Lobby call close setup

Sets the amount of time before the doors close after a lobby call is answered when on normal operation.
DTL value overrides DTHF/DTHR value when answering a hall call at the lobby floor.
Recommend DTL is set equal to or greater than DTHF/DTHR and DTCF/DTCR.
DTL EEPROM Door time close. (VALUE)
Set value for door close time.
The time is set in 100ms increments.
1e: 00011110 = 3000ms, "3 seconds"
32: 00110010 = 5000ms, "5 seconds"
90: 10010000 = 14400ms, "14.4 seconds"
(01 to FF valid values.)

DTRF - Door Time Recall Front setup

Sets the amount of time before the front doors close after returning to HR or HR1 floor and lift not being
switched to IND or CFS.
The time is set in 100ms increments.
Eg. 32: 00110010 = 5000ms, "5 seconds"
See also Inputs-Outputs SIN3

DTRR - Door Time Recall Rear setup

Sets the amount of time before the rear doors close after returning to HR or HR1 floor and lift not being switched
to IND or CFS.
The time is set in 100ms increments.
Eg. 32: 00110010 = 5000ms, "5 seconds"
See also Inputs-Outputs SIN3