Counting Method "00" - Magnet Counting - ECD 100-181 Manual

Table of Contents

Advertisement

M O T I O N

Counting Method "00" - Magnet Counting.

EEProm MSL setting "00"
The controller counts its position within the lift shaft using the DZ – Door Zone Input, MSU – Magnet Switch Up
Input, MSD – Magnet Switch Down Input, TSL – Top Slowing Limit and BSL – Bottom Slowing Limit.
If the lift is stationary or running down and BSL input is removed, the lift shall reset to the bottom floor. If
running down in fast speed, the fast speed inputs shall be turned off.
If the lift is stationary or running up and TSL input is removed, the lift shall reset to the top floor. If running up in
fast speed, the fast speed inputs shall be turned off.
The shaft information at floor level must be as per the Counting Method "00" Shaft Layout drawing in
that the MSD and MSU vanes must be within the door zone. See the diagram; "
Shaft Layout" at the end of this section.
If the lift was to leave the bottom floor in the up direction heading to the third landing it would count as follows.
• While traveling up fast all MSD out of the DZ shall be ignored.
• As the lift travels up fast and passes MSU slowing magnet for level 2, the advance count is shown by
transistor outputs 1P-8P.
• As the lift travels up fast and passes the DZ magnet for level 2 (MSU and MSD ignored/masked by DZ)
the position count as shown on the LCD shall increment to level 2.
• As the lift travels up fast and passes MSU slowing magnet for level 3, the advance count is shown by
transistor outputs 1P-6P. As the lift advance counts, slowing shall be initiated for level 3.
• The lift shall now level into the third floor. The position count shall increment to level 3 when the DZ
vane is entered. The lift shall remain running until both MSU and MSD are on. LEV relay output shall
turn on when either MSU or MSD is on.