E E P R O M S E T T I N G S
20: 00100000 (Level 3)
10: 00010000 (Level 4)
08: 00001000 (Level 5)
04: 00000100 (Level 6)

TOP - Top floor setup

TOP EEPROM
Top floor number (VALUE)
Set value to number floors served. (02 to 06 are valid values).
Lift resets to "TOP" value when TSL limit is activated.
02: 00000010 (Level 2)
03: 00000011 (Level 3)
04: 00000100 (Level 4)
05: 00000101 (Level 5)
06: 00000110 (Level 6)

UCMF - Up Call Mask (Front doors) setup

This setting lets you define the UP call(s) of front doors floors which the lift can serve.
With this setting you may disable UP hall calls to front doors floors not allowed.
UCMF EEPROM Up call mask. Front doors floors allowed. (MASK) Up calls allowed for this lift only.
80: 10000000 (Level 1u)
C0: 11000000 (Level 1u,2u)
E0: 11100000 (Level 1u,2u,3u)
F0: 11110000 (Level 1u,2u,3u,4u)
F8: 11111000 (Level 1u,2u,3u,4u,5u)

UCMR - Up Call Mask (Rear doors) setup

This setting lets you define the UP call(s) of rear doors floors which the lift can serve.
With this setting you may disable UP hall calls to rear doors floors not allowed.
UCMR EEPROM Up call mask. Rear doors floors allowed. (MASK) Up calls allowed for this lift only.
80: 10000000 (Level 1u)
C0: 11000000 (Level 1u,2u)
E0: 11100000 (Level 1u,2u,3u)
F0: 11110000 (Level 1u,2u,3u,4u)
F8: 11111000 (Level 1u,2u,3u,4u,5u)

XTM - Extend run time short floor run

If a short floor exists where the lift starts slowing prior to reaching full speed, a long creep into floor may occur.
RTM setting, in conjunction with XTM setting, can reduce this long creep time by holding in the fast speed relay
for a defined time after the initial slowing point.
Setting RTM. – Look at Ram address R:72. (Motion Timer). See RTM for access to R:72.
When performing the shortest floor run take note of the highest value reached (in hex). Add approx. 5 to this value
and set RTM to this value.
If slowing is obtained before the value in RTM is reached, the fast speed relay will be held up for extra time as
defined by XTM.
Set XTM to 20. If the lift fails to slow down to leveling speed before reaching the floor, (ie, fast speed relay is
being held up too long) reduce XTM value. If there is still too much creep (ie, fast speed relay is being held up not
long enough) increase XTM time. Continue until desired result is obtained.

ZON - Zoning/Parking floor setup

ZON is only used in duplex configurations.
After the zone time period as defined by ZTM, a lift shall zone to floor defined by LOB. If LOB floor is occupied
then the lift shall alternatively zone to ZON floor.