E E P R O M S E T T I N G S
08: 00001000 Not used. Default to 0.
10: 00010000 Not used. Default to 0.
20: 00100000 DCBR. Door close rear input inverted
40: 01000000 DOBR. Door open rear input inverted
80: 10000000 EDPR. Light ray rear input inverted
eg. 42: 01000010 = Both DOBF and DOBR door open button inputs inverted.
COD – Parameter lockout function
To stop unauthorised adjustments to the EEprom parameters the COD and LCK parameters are used.
COD and LCK must both be set to default values to allow other parameters to be adjusted.
See also Eeprom setting LCK
COD default. 89: 10001001
LCK default. 67: 01100111

DCMF - Down Call Mask (Front doors) setup

DCMF EEPROM (MASK) Front doors down hall calls allowed for this lift only.
This setting lets you define the DOWN front doors floors which the lift can serve via DOWN HALL CALLS
Set bits to a "1" hall call allowed or a "0" for not allowed.
40: 01000000 (2d)
60: 01100000 (2d,3d)
70: 01110000 (2d,3d,4d)
78: 01111000 (2d,3d,4d,5d)
7C: 01111100 (2d,3d,4d,5d,6d)

DCMR - Down Call Mask (Rear doors) setup

DCMR EEPROM (MASK) Rear doors down hall calls allowed for this lift only.
This setting lets you define the DOWN rear doors floors which the lift can serve via DOWN HALL CALLS
Set bits to a "1" hall call allowed or a "0" for not allowed.
40: 01000000 (2d)
60: 01100000 (2d,3d)
70: 01110000 (2d,3d,4d)
78: 01111000 (2d,3d,4d,5d)
7C: 01111100 (2d,3d,4d,5d,6d)

DLI - Door Limit Invert setup

DLI is only valid when DLM is set to 00, 03 or 04. See also EEprom setting DLM.
DLI setting is used to invert the DFOF/DFOR and DFCF/DFCR inputs when normally open (n/o) door limit
contacts are used.
DLI EEPROM Door limit invert. (MASK)
DLI: 00 "Limits not inverted."
DLI: 01 " Limits inverted." Any setting other than 00 shall default to inverted limits.
DLI set to 00 - Limits not inverted. Using n/c limits.
Doors fully open – DFCF/DFCR LED will be on. DFOF/DFOR LED will be off
Doors fully closed – DFCF/DFCR LED will be off. DFOF/DFOR LED will be on
Doors midway – DFCF/DFCR LED will be on. DFOF/DFOR LED will be on
DLI set to 01 - Limits inverted. Using n/o limits.
Doors fully open – DFCF/DFCR LED will be off. DFOF/DFOR LED will be on
Doors fully closed – DFCF/DFCR LED will be on. DFOF/DFOR LED will be off