Hfsr - Hall Fire Service (Rear Doors) Return Floor Setup; Hrf - Hospital / Hall Recall Front Doors; Hrr - Hospital / Hall Recall Rear Doors; Lck - Parameter Lockout Function - ECD 100-181 Manual

Table of Contents

Advertisement

E E P R O M S E T T I N G S

HFSR - Hall Fire Service (Rear doors) Return floor setup

This sets the hall fire service return rear doors floor activated when HFS input is active whilst in normal mode and
HFSR has a setting floor.
HFSR...EEPROM Hall Fire Service (Rear doors) floor. (MASK)
00: 00000000 (No setting floor)
80: 10000000 (Level 1)
40: 01000000 (Level 2)
20: 00100000 (Level 3)
10: 00010000 (Level 4)
08: 00001000 (Level 5)
04: 00000100 (Level 6)
Note: Set either HFSF OR HFSR. DO NOT set both of them.
HRF – Hospital / Hall Recall Front doors
This sets the Hospital Recall floor for the front doors when lift is in HR mode.
See also Inputs-Outputs SIN3 and Eeprom settings HRR
If HRF is set, HRR MUST be 00 or recall shall not operate.
eg. 40: 01000000 (Level 2)
HRR – Hospital / Hall Recall Rear doors
This sets the Hospital Recall floor for the rear doors when lift is in HR mode.
See also Inputs-Outputs SIN3 and Eeprom settings HRF
If HRR is set, HRF MUST be 00 or recall shall not operate.
eg. 20: 00100000 (Level 3)
LCK – Parameter lockout function
To stop unauthorised adjustments to the EEprom parameters the LCK and COD parameters are used.
LCK and COD must both be set to default values to allow other parameters to be adjusted.
See also Eeprom setting COD
LCK default. 67: 01100111
COD default. 89: 10001001

LOB - Lobby floor setup

This signal sets the master zoning floor. After the zone time period as defined by ZTM, a lift shall zone to floor
defined by LOB, if unoccupied. If LOB floor is occupied then the lift shall alternatively zone to ZON floor.
A lift shall zone to floor defined by LOB and ignore ZON, when working in simplex.
LOB EEPROM
Lobby floor. (MASK) Master zoning floor.
LOB must be set to the same value in all lifts belong to the group.
00: 00000000 (No zoning). To disable zoning set "LOB" and "ZON" to "00".
80: 10000000 (Level 1)
40: 01000000 (Level 2)
20: 00100000 (Level 3)
10: 00010000 (Level 4)
08: 00001000 (Level 5)
04: 00000100 (Level 6)

L.# - Lift Number setup

Lift number setup.
Example: In a 2 car group you must have one lift set to 01 and the other set to 02. It doesn't matter which way
around they are as long as each lift is different.