E E P R O M S E T T I N G S
Spares
--1 EEPROM Spare
--2 EEPROM Spare
--3 EEPROM Spare
--4 EEPROM Spare
--5 EEPROM Spare
StF - Start Fast
Number of pulses (in hex) it takes to reach fast speed
StF
EEPROM
Start Fast pulses. (VALUE)
Eg. 30: 00110000 (30 pulses in hex or 48 in decimal)
See also Section 6: Motion – EEprom MSL setting "01"
StM - Start Medium
Number of pulses (in hex) it takes to reach medium speed.
StM
EEPROM
Start Medium pulses. (VALUE)
Eg. 20: 00100000 (20 pulses in hex or 32 in decimal)
See also Section 6: Motion – EEprom MSL setting "01"
SlF - Slow Fast
Number of pulses (in hex) it takes to slow from fast speed.
SlF
EEPROM
Slow Fast pulses. (VALUE)
Eg. 30: 00110000 (30 pulses in hex or 48 in decimal)
See also Section 6: Motion – EEprom MSL setting "01"
SlM - Slow Medium
Number of pulses (in hex) it takes to slow from medium speed.
SlM
EEPROM
Slow Medium pulses. (VALUE)
Eg. 20: 00100000 (20 pulses in hex or 32 in decimal)
See also Section 6: Motion – EEprom MSL setting "01"
ST2 - Star Delta Changeover Time setup
Star connected motor running time.
The amount of time the motor runs in Star, before changing to Delta.
ST2 EEPROM Star Delta time. (VALUE)
The time is set in 100ms increments.
08: 00001000 = 800ms
0a: 00001010 = 1000ms, "1 second"
12: 00010010 = 1800ms, "1.8 seconds"
ST2 - VF Drive setting 06,07,08 end run time
Valid only when Eeprom setting "DRV" is set to "06, 07, 08".
This sets the amount of time after a run for the Up/Dn relays to drop in 10ms increments.
Set between 01 & ff .
ST2 value must be greater than SDX value
TCC - Top Car Call setup
TCC
EEPROM
Top car call for the "TOP CALL" button on the circuit board (MASK)
Top floor served for this lift only.
The controller shall enter a car call to this setting when the "TOP CALL'' button on the circuit board is pressed.
40: 01000000 (Level 2)