Hach sc200 User Manual page 599

Hide thumbs Also See for sc200:
Table of Contents

Advertisement

G2...(S) 2-way Globe Valve, Bronze or Stainless Steel Trim
Technical Data
Service
Flow characteristic
equal percentage
Action
Sizes
End fi tting
Materials
Body
bronze
Seat
bronze
Stem
stainless steel
Plug
brass
Packing
spring loaded TFE
Disc
composition (EPDM)
ANSI class
Leakage
Max steam inlet
35 psi (241 kPa)
Media temperature
Water
20°F to 250°F
(-7°C to 120°C)
Maximum ΔP*
35 psi (241 kPa)
Water
Steam
20 psi (138 kPa)
Rangeability
G2(S) 100:1
Valve weights
G212(S), G213(S), G214(S), G215(S)
G219(S), G220(S)
G224(S), G225(S), G232(S)
G240(S), G250(S)
*(50% or more open)
G2...(S) 2-way Flow Patterns
Flow Direction
800-543-9038 USA
8
G2
G2...S
chilled or hot water, 60% glycol, steam
linear
stem up - open A to AB
½" to 2"
NPT female ends
bronze
stainless steel
stainless steel
stainless steel
spring loaded TFE
Tefl on
ANSI 250 (up to 400 psi below 150°F)
ANSI class IV
100 psi (689 kPa)
20°F to 300°F
(-7°C to 149°C)
35 psi (241 kPa)
35 psi (241 kPa)
2 lbs
3 lbs
5.5 lbs
13 lbs
Stem Up - Open A to AB
Application
This valve is typically used in Air Handling Units on heating or cooling coils and Fan Coil
Unit heating or cooling coils. Some other common applications include Unit Ventila-
tors, VAV Box reheat coils and bypass loops. This valve is suitable for use in a hydronic
system with variable fl ow.
Bronze and stainless steel trim valves can be used for steam applications, depending on
actuator and close-off combinations.
Valve Nominal Size
C
Inches DN [mm]
v
0.4
½
1.3
½
2.2
½
4.4
½
5.5
¾
7.5
¾
10
1
14
1
20
28
40
2
Dimensions
Valve Body
G212(S)-G215(S)
G219(S)-G220(S)
G224(S)-G225(S)
G232(S)
G240(S)
G250(S)
Piping
The valves should be mounted in a weather-protected area in a location that is within
the ambient limits of the actuator. Allow suffi cient room for valve with actuator and
for service. Please allow 12" for complete actuator/linkage removal. The G2(S) and
G3(D) preferred mounting position of the valve is with the valve stem vertical above
the valve body, for maximum life. However, the assemblies can be mounted with the
valve stem vertical or horizontal in relation to the pipe. The actuators should never be
mounted underneath the valve, as condensation can build up and result in a failure of
the actuators. Do not reverse fl ow direction.
866-805-7089 CANADA
Type
Suitable Actuators
Non-
2-way NPT
Spring
15
G212(S)
15
G213(S)
15
G214(S)
15
G215(S)
20
G219(S)
20
G220(S)
25
G224(S)
25
G225(S)
32
G232(S)
40
G240(S)
50
G250(S)
Valve Nominal Size
Dimensions (Inches [mm])
Inches DN [mm]
A
½"
15
3.06" [78]
¾"
20
3.62" [92]
1"
25
4.62" [117]
32
4.62" [117]
40
5.37" [137]
2
50
6.12" [156]
203-791-8396 LATIN AMERICA
Spring
Electronic
Fail- Safe
B
1.06" [27]
1.06" [27]
1.12" [29]
1.37" [35]
1.50" [38]
1.56" [40]

Hide quick links:

Advertisement

Table of Contents
loading