F8- Zone Editor
The specific zone is selected under F2 - Add Setpoints.
This screen enables user to program zone relays for a latched or
unlatched function.
If latched function is selected, relay is unlatched by supplying a
closed contact to the corresponding input or by pressing the up
arrow (▲) key.
I0- Unlatch Zone 1
I1- Unlatch Zone 2
I2- Unlatch Zone 3
I3- Unlatch Zone 4
I4- Unlatch Zone 5
Figure 6-22. Zone Editor - Set Relays as Latched or Unlatched
F6- Skips to next screen
When zone relays are set as unlatched, then Zone relays can be
set to On-Delay or Off-Delay.
On-Delay:relay activates only if alarm exists for the set time.
Off-Delay (Typically used for fan control): relay stays energized
for the set delay time after the alarm condition clears.
NOTE: Selecting latching disables ON delay, OFF delay, and delay
time settings.
Times are adjustable from 0 seconds to 15 minutes.
After entering time delay, press enter
6-18
I5- Unlatch Zone 6
I6- Unlatch Zone 7
I7- Unlatch Zone 8
I8- Unlatch Zone 9
I11 -Ultima X3 monitor
acknowledge
I12- Horn silence
. f or data to display.