Effect Of Ageing On Lighting Equipment - ABB i-bus KNX Product Manual

Dali light controller dlr/s 8.16.1m
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Planning and application
4.5

Effect of ageing on lighting equipment

Every fluorescent lamp ages in service. The lighting power of the fluorescent lamps degrades, i.e. a lower
brightness is produced at the same control value. This can even mean that the setpoint originally required
can no longer be achieved with maximum control. For this reason, the lighting is to be dimensioned, so
that the required setpoint brightness can be achieved until the luminaires are routinely exchanged.
In principle, the ageing lighting equipment has no effect on the control circuit. If a lower brightness level is
achieved due to ageing of the lighting equipment with the same control, the DLR/S, e.g. via a DLR/S
lighting group, will continue to increase the level of artificial light until the setpoint brightness is achieved.
However, it must be considered that the characteristic of the lighting equipment changes with ageing.
The characteristic was determined during the calibration procedure and is the basis for the control
algorithm. In this way, it is possible that light control discrepancies result.
The following approach results
The recorded characteristic of the artificial light is calculated with the control value. Assuming that the lamp
generated 30 % less light, the value of the characteristic would be 1.33 times larger than the real value.
The DLR/S then assumes that the level of daylight is lower than it actually is. There appears to be less
daylight needing to be compensated.
With a compensation factor of 30 (for the control algorithm 0.3), an approximate reduction of the setpoint
value by 10 % would be achieved. The DLR/S would control to a level which is too dark by 10 %.
In concrete terms, this would mean that a light control originally set by the DLR/S to 500 lx will now only
provide a brightness value of 450 lx. Furthermore, the tolerances of the DALI Light Controller as described
in chapter
Note
The burn-in time, where the light may not be dimmed, must be complied with to ensure that the most
stable possible lighting equipment performance is assured. During the burn-in time, which usually lasts
between 50 and 100 hours, the lighting equipment must be operated at 100 % brightness.
The burn-in time of a luminaire can be obtained from the manufacturer.
164 2CDC 507 100 D0202 | DLR/S 8.16.1M
Technical data
, page 12, apply.