Commissioning
Group x brightness value of Scene (x = 1...16)
Options:
Note
The options 100 % (255) to 0 % (OFF) are only visible if the parameter Overwrite scene on download is
set to Yes. With the option No, the possible settings are reduced to No change (no member in this
Scene) and Member in this scene.
This parameter defines the brightness value that the lighting group sets itself to when a scene is recalled.
No change (not a member in this scene): This lighting group does not belong in this scene. During a
scene recall, the lighting group is not influenced. The current brightness value of the lighting group
remains unchanged and, even when the scene is stored via the KNX, the brightness value of this
group is not saved.
100 % (255)...0 % (OFF): The lighting group belongs to the scene. During a scene recall, the lighting
group is set to the brightness value parameterized here. If the set brightness value is above or below
the set maximum or minimum dimming value of the respective lighting group (see the
window Gx
120 2CDC 507 100 D0202 | DLR/S 8.16.1M
No change (not a member in this scene)
100 % (255)
99 % (252)
...
1 % (3)
0 % (OFF)
Group, page 67), the respective brightness value is saved in the scene.