ABB i-bus KNX Product Manual page 188

Dali light controller dlr/s 8.16.1m
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Planning and application
In order to get a point of reference for the individual control parameterization, in the following table, you will
find a list of the fixed parameterized settings in the DLR/S, as well as the individually adjustable values for
the Changing brightness during lighting control (fast
Changing brightness during light control
(correction speed)
Step time for fast approach [0.1 s...2.0 s]I
Step time for slow approach [1 s...10 s]
Setpoint/actual difference, for changeover of fast/slow
approach [0...50]
Maximum increment size of a control step [1...10]
Setpoint/actual difference, up to which control is with
max. step width [10...255]
Deviation actual value from nominal
value for starting controlling [0...30]
1)
The selection fast is only possible if the light controller does not control any further slaves via the communication object
Master brightness value. The setting is made in parameter window - Gx Light controller with the parameter Light controller
controls other dimmer actuators as "master" other dimmer actuators).
186 2CDC 507 100 D0202 | DLR/S 8.16.1M
1
), medium, slow and the individual setting):
Fast
Medium
As quickly as
0.5
possible.
2
3
20
20
1
1
30
30
1
1
Individual
Slow
setting
1
1
4
4
20
20
1
1
30
30
1
1

Advertisement