Planning and application
The reaction of the Slave function after KNX voltage recovery can be parameterized: In the
window - Gx
the lighting group after KNX voltage recovery can be set in the
If the Active mode is parameterized, the parameterized brightness value is initially set after KNX voltage
recovery. Subsequently, the next brightness value received via communication object Brightness value of
Slave is then set.
In the following table, the response to received telegrams with the parameterized Slave function is shown.
Operating situation
or
Communication objects
Download (start)Download
(start)
Download (end)
Voltage failure
KNX bus
Voltage

recovery
Voltage failure
DALI
or
Gateway
Voltage

operation
recovery
ON
Switch
OFF
Relative dimming
Brightness value
Brightness value of slave
0
Slave function
activate
1
Recall scene
Slave, page 112, you can set whether operation is active or inactive. The brightness value of
Inactive
(Function Activate Slave = 0)
Switch-on value
OFF
Dimming
Brightness value
No reaction
No reaction
Current

brightness value of slave
 → Active
Scene
Parameter window - Gx
Additional function Slave
Active in standby
(Activate slave mode = 1)
Such as KNX bus voltage failure
Such as KNX bus voltage recovery
Parameterizable:- Brightness value - Gx Fault
Programmable:
- Mode: - Gx Slave
- Brightness value - Gx Fault
Programmable:
- Brightness value - Gx Fault
Programmable:
- Mode: - Gx Slave
- Brightness value - Gx Fault
→ Active,
current Brightness value of slave is
set
OFF, remains in standby
Dimming, remains in standby
Brightness value, remains in standby
No reaction
→ Inactive
Current

brightness value of slave
 → Active
Scene
Parameter
Fault, page 81.
Active and ON (running)
(Function = 1)
Programmable:
- No reaction
- Goes to standby and sets 

switch-on value
OFF and goes to standby
Programmable:
- No reaction
- Goes to standby and dims
Programmable:
- No reaction
- Goes to standby and sets 

brightness value
Brightness value of slave 

is set
→ Inactive
Current 

brightness value of slave
Programmable:
- No reaction
- Goes to standby and starts
scene
DLR/S 8.16.1M | 2CDC 507 100 D0202 191