ABB i-bus KNX Product Manual page 143

Dali light controller dlr/s 8.16.1m
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
No.
26
This communication object is enabled if, in the
Burn-in object "Burn-in lamp/status" is parameterized with the Yes option and a status message about the burn-in process
is also required.
The communication object also features, in addition to the properties of the communication object Burn-in lamps described
previously, the property that the burn-in status can be requested or sent on the KNX in accordance with the
parameterization.
Telegram value:
27
This communication object is always enabled. However, it is only required for the artificial light and daylight calibration of a
constant light control.
Using this communication object, the communication objects Daylight calibration or Artificial light calibration are enabled for
receipt of a telegram, i.e., the DLR/S only performs daylight or artificial light calibration if the communication object Enable
controller calibration has received a telegram with the number of the respective lighting group (1...8) beforehand. This
ensures that calibration is not performed unintentionally.
The readiness to receive a telegram for the activation of the daylight or artificial light calibration remains in effect for 1 hour,
if a calibration request has not been received and has taken place beforehand via the communication objects Calibration
artificial light or Calibration daylight.
Telegram value:
Function
Burn-in lamp/Status
0 = Deactivate Burn-in function or no lighting group is in the burn-in state.
1 = Activate Burn-in function or at least one lighting group is in the
burn-in state.
Enable controller calibration
1...8
= The numeric value enables the lighting group, via the communication objects
Calibration artificial light or Calibration daylight, to perform a calibration
of the constant lighting control.
0
=
Immediately resets the readiness to receive for the communication objects Calibration
daylight and
Calibration artificial light, i.e. telegrams to the communication objects
Calibration artificial light or Calibration daylight are not actioned.
Object name
DALI output
Parameter window
Central, page 53, the parameter Enable central function
DALI output
Data type
Flags
1 bit
C, W
DPT 1.010
1 byte
C, W
Non DPT
DLR/S 8.16.1M | 2CDC 507 100 D0202 141

Advertisement

Table of Contents
loading

Table of Contents