ABB i-bus KNX Product Manual page 50

Dali light controller dlr/s 8.16.1m
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
"Request status values"
Options:
Via this communication object, all status messages can be requested, provided that they have been
parameterized with the option After a change or request or On request.
No: The 1 bit communication object Request status values is not enabled.
Yes: The 1 bit communication object Request status values is enabled. The following parameter
appears:
Enable staircase lighting time curve
(one curve for entire device)
Options:
The DLR/S has the option of implementing a staircase lighting time curve incorporating a dimming up and
pre-warning phase. This curve can be recalled individually, however, for every lighting group with the
switch telegram of the lighting group. The staircase lighting time curve is defined in the next parameter that
appears with the Yes option.
No: In the DLR/S, Staircase lighting is not available.
Yes: The DLR/S has a Staircase lighting function. The time curve is defined in the next parameters.
48 2CDC 507 100 D0202 | DLR/S 8.16.1M
No
Yes
Request with object value
Options:
0
1
0 or 1
This parameter defines the value at which the communication object Request status values is
triggered. This function offers the option of providing up-to-date values to a visualization system, for
example.
0: Sending status messages is requested with the value 0.
1: Sending status messages is requested with the value 1.
0 or 1: Sending status messages is requested with the values 0 or 1.
No
Yes
Scenes 13 and 14 are used for function staircase lighting
Note
If the Staircase lighting function is used in the DLR/S, scenes 13 and 14 are used for this
function. These are then no longer available as "normal" scenes.