ABB i-bus KNX Product Manual page 15

Dali light controller dlr/s 8.16.1m
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Device technology
Operating and display elements
Degree of protection
Protection class
Isolation category
KNX safety extra low voltage
DALI voltage
Temperature range
Environmental conditions
Design
Mounting
Installation position
Weight
Housing, color
Approvals
CE mark
1)
Maximum load corresponds to 64 DALI devices at 2 mA each.
2)
The length relates to the entire routed DALI control cable.
The maximum values are rounded off and relate to the resistance value. EMC influences are not considered. For this reason, the values should be
considered as absolute maximum values.
3)
Rooms are lit up differently by the incidental daylight and the artificial light of the lamps. Not all the surfaces in the rooms, e.g. walls, floor and
furniture, reflect the light which falls on them in the same manner. Accordingly, even though there is an exactly calibrated constant light control in
daily operation, deviations to the setpoint value may occur. These deviations may be up to +/- 100 lx, should the current ambient conditions in the
room, and accordingly the reflection properties of the surfaces (paper, people, reorganized or new furniture), differ significantly from the original
ambient conditions at the time of calibration. Deviations may also occur if the light sensor is influenced by direct or reflected light falling on it, which
is not influenced or only slightly influenced by the surfaces in the detection range of the light sensor.
4)
Cannot be measured directly on the digital multimeter, as there is not a constant DC voltage due to the DALI telegrams. Measure with a CRO for
correct results. One exception is the KNX download phase. In this phase, no DALI telegrams are sent, whereby the DALI voltage is constantly
present on the DALI output.
Button/LED
Button
/LED
Button
Button
Button
Button
LED
LED
...
16 LED
IP 54
II
Overvoltage category
Pollution degree
SELV 24 V DC
Typical 16 V DC (9.5...22.5 V DC)
No-load voltage
Lowest supply current at 11.5 V
Highest supply current
Power
Storage
Transport
Humidity
Modular installation device (MDRC)
Dimensions
Mounting width
Mounting depth
On 35  mm mounting rail
Any
0.26 kg
Plastic housing, gray
KNX to EN 50 090-1, -2
EN 62 386 (Part 101 and 102)
In accordance with the EMC guideline and low
voltage guideline
For assignment of the physical address
For switchover between manual operation and
KNX operation
Switch to next lighting group
Switch ON or dim UP
Switch OFF or dim DOWN
Detect devices
Display for operation readiness
DALI operating voltage display
Lighting group 1...16 display
Compliant to EN 60 529
Compliant to EN 61 140
III to EN 60 664-1
2 to EN 60 664-1
To DIN EN 60 929 and DIN EN 62 386
4)
16 V DC
160 mA
230 mA
-5 °C...+45 °C
-25...+55 °C
-25...+70 °C
Maximum 95 %, no condensation allowed
Modular installation device, ProM
90 x 108 x 64.5 mm (H x W x D)
6 x 18 mm modules
68 mm
Compliant to EN 60 715
Certification
DALI
DLR/S 8.16.1M | 2CDC 507 100 D0202 13

Advertisement

Table of Contents
loading