ABB i-bus KNX Product Manual page 98

Dali light controller dlr/s 8.16.1m
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
Reaction on DALI voltage or
light controller supply voltage recovery
Options:
This parameter determines the state that the Staircase lighting function assumes after DALI or light
controller supply voltage recovery.
After a DALI or light controller operating voltage recovery, the lighting group first assumes the state as
parameterized in the
for the Staircase lighting function:
Not activated: The Staircase lighting function is not reactivated after DALI or light controller operating
voltage recovery. The lighting group behaves like a normal lighting group without additional functions.
Activate standby: The Staircase lighting function is activated after DALI or light controller operating
voltage recovery and is in standby. The lighting group can be started by an ON telegram or a renewed
activation via the communication object Activate stairc. light./Status.
96 2CDC 507 100 D0202 | DLR/S 8.16.1M
Relative dimming
Options:
No reaction
Function switches to standby
If the Staircase lighting function is activated, the parameter can be used to define the reaction to
dimming telegram to the communication object Relative dimming.
No reaction: Dimming telegrams are ignored.
Function switches to standby: A dimming telegram ends the Staircase lighting function, and the
lighting group executes the dimming telegram. The Staircase lighting function is latent and
waits until a renewed activation via the communication object Activate stairc. light./Status or via
an ON telegram to the communication object Switch.
Recall scene
Options:
No reaction
Function switches to standby
When the activated Staircase lighting function is activated, the parameter can be used to define the
reaction to a scene recall on the communication object Recall scene.
No reaction: A scene recall is ignored.
Function switches to standby: A scene recall ends the Staircase lighting function, and the
DLR/S executes the dimming telegram. The Staircase lighting function is latent and waits until
a renewed activation via the communication object Activate stairc. light./Status or via an ON
telegram to the communication object Switch.
Not activated
Activate standby
Activate and ON
Previous state to malfunction
Parameter window - Gx Fault,
page 81. The following states can be parameterized