ABB i-bus KNX Product Manual page 132

Dali light controller dlr/s 8.16.1m
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
No.
8
This communication object is enabled if, in the
time for dimming (Fade Time) is parameterized with the option KNX format in 100 ms [value 0...65,535/0...9050 ms].
Using this communication object, it is possible to define the fade time as described in the DALI standard EN 62386-102 via
the DALI control by using the KNX, so that the intended DALI devices use the DALI fade times.
Please note that it is not the sent KNX value that is used in the DALI, but rather the nearest DALI value. The DLR/S
performs a mathematical rounding off in order to determine the most suitable DALI value.
Telegram value:
The fade time is specified as the time duration required for changing the lamp power from the current brightness value to
the required target brightness. In the case of a switched off lamp, the preheat and ignition time is not included in the fading
time.
The set dimming time is retained at light controller supply voltage failure.
On KNX bus voltage failure the dimming time is lost and must be set once again. The value 5.7 s is set as a default value
until a new value is received.
130 2CDC 507 100 D0202 | DLR/S 8.16.1M
Function
Fade time (KNX format)
[Value 0...65,535/0...9050 ms]
0...65,535 x 100 ms, KNX value that is transformed into one of the 16 fade times of the DALI
standard.
Telegram value
in 100 ms
0...3
4...8
9...12
13...17
18...24
25...34
35...48
49...68
69...96
97...136
137...193
194...273
274...386
387...546
547...772
>773
Object name
General
Parameter window
Central, page 53, the parameter Object format of flexible
Active fading time [s] to EN 62386-102
Jump to
0.7
1.0
1.4
2.0
2.8
4.0
5.7
8.0
11.3
16.0
22.6
32.0
45.3
64.0
90.5
Data type