Commissioning
"Fault DALI"
Options:
Using this communication object, a fault of the DALI communication of the output, i.e. a short-circuit
> 500 ms or a data collision, can be sent or read, for example for diagnostic purposes. Individual fault
indication objects are available for a ballast/lamp fault.
No: The communication object Fault DALI is not enabled.
Yes: The communication object Fault DALI is enabled. As soon as there is a DALI fault on the output,
it is indicated by a 1 in the communication object Ballast fault. The following parameter appears:
"Lamp Fault"
Options:
Via this communication object, a fault of a lamp for the DALI output can be sent or read.
No: The communication object Lamp fault is not enabled.
Yes: The communication object Lamp fault is enabled. As soon as there is a lamp fault on the output,
it is indicated by a 1 in the communication object Lamp fault. The following parameter appears:
64 2CDC 507 100 D0202 | DLR/S 8.16.1M
Send
Options:
After a change
On request
After a change or request
After a change: The status is sent via the communication object after a change.
On request: The status is sent after a request by the communication object Request status
values.
After a change or request: The status is sent via the KNX when the status changes or the
status is requested via the communication object Request status values.
No
Yes
Send
Options:
After a change
On request
After a change or request
After a change: The status is sent via the communication object after a change.
On request: The status is sent after a request by the communication object Request status
values.
After a change or request: The status is sent via the KNX when the status changes or the
status is requested via the communication object Request status values.
No
Yes