ABB i-bus KNX Product Manual page 153

Dali light controller dlr/s 8.16.1m
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
No.
198...204
This communication object is enabled if, in the
enabled.
A telegram, which is received via the communication object from the DLR/S, recalls scene x or y. Only the lighting groups
which also belong to the scene are activated.
Telegram value:
The standard brightness values of a scene are parameterized in the
Overwrite scene on download is selected with the Yes option, the scene values parameterized by the ETS are written to the
DALI devices of the lighting groups with a download. Any values saved on the KNX are overwritten and lost.
205...211
This communication object is enabled if, in the
enabled.
A telegram, which is received via this communication object from the DLR/S, causes the DLR/S to save the current
brightness values of the lighting groups which are part of the scene as new scene brightness values for the scene and to
write in the corresponding lighting groups of the devices. The saved scene values possibly received via the ETS during a
download are overwritten and are lost.
Telegram value:
The scene that is set manually once via the KNX can be protected against overwriting with a download by setting the No
option for Overwrite scene on download in the
parameterized in the ETS are not written into the DALI devices of the lighting groups. The scene brightness values set
manually via the KNX are retained.
Function
Recall scene
0 = Recall first scene number (x = odd scene number)
1 = Recall second scene number (y = even scene number)
Store scene
0 = Saving of the scene brightness values of the first scene no. (x)
1 = Saving of the scene brightness values of the second scene no. (y)
Note
Not all 16 lighting groups are considered when saving. Only the lighting groups, which belong to the scene,
are considered.
Thus, for example, the lighting groups in adjacent rooms, which are not part of the scene, are not changed.
Object name
Scene x/y
x = 1, 3...13
y = 2, 4...12
Scenes, page 117, 
the respective scenes have been
Parameter window
Parameter window Scene
Scene x/y
x = 1, 3...13
y = 2, 4...12
Scenes, page 117, 
the respective scenes have been
Parameter window
Parameter window Scene
x, page 118. In this case, the brightness values
Data type
Flags
1 bit
C, W
DPT 1.022
x, page 118. If the option
1 bit
C, W
DPT 1.022
DLR/S 8.16.1M | 2CDC 507 100 D0202 151