Commissioning
Status response of function Slave
Options:
This parameter defines whether the status of the Slave function of the lighting group is sent on the KNX.
For this purpose, the communication object Activate Slave/Status is enabled.
No: The state of the Slave function is not actively sent on the KNX.
Yes: via object "Activate Slave/Status": The common communication object Activate Slave/Status
receives a telegram with the value 1 to activate the Slave function and simultaneously sends the
current status of the Slave function actively on the KNX. It is possible to parameterize when the status
is sent on the KNX. The following parameter appears:
116 2CDC 507 100 D0202 | DLR/S 8.16.1M
No
Yes: via object "Activate Slave/Status"
Send
Options:
After a change
On request
After a change or request
After a change: The status is sent via the communication object after a change.
On request: The status is sent after a request by the communication object Request status
values.
After a change or request: The status is sent via the KNX when the status changes or the
status is requested via the communication object Request status values.