CHAPTER 5: SETPOINTS
Note
NOTE
Note
NOTE
5.2.7

Front Panel

FRONT PANEL
750 FEEDER MANAGEMENT RELAY – INSTRUCTION MANUAL
Continuous Mode: Enabled by setting
sampling time the logger will record the actual value(s) programmed and store them
in the log. Up to 4096 data samples per channel will be recorded after which the
oldest data is replaced by newly sampled data.
Trigger Mode: Enabled by setting
actual value(s) for up to the last 15 events are recorded, each in a separate buffer. The
amount of pre-trigger data to record is also selectable. Before the trigger occurs, pre-
trigger data is gathered as required. When the programmed trigger condition takes
place, data is collected until the buffer is filled, pre-trigger data collection begins in the
next buffer and the relay then waits for the next trigger. Once all buffers have been
filled, the oldest data is overwritten when a new trigger occurs.
The
BUFFER ORGANIZATION
mode. The
BUFFER ORGANZIATION
channel stored for each trigger. For example, "4 x 1024" indicates that the last three
triggers with 1024 data samples per channel can be stored in memory. Note that one
buffer must be reserved for capturing the next event. The
selects the amount of each buffer to be allocated for pre-trigger data. If set to "0%", data
collection effectively starts once the trigger occurs. If set to 100%, only pre-trigger data will
be recorded in the buffer.
If a trigger occurs before the programmed amount of pre-trigger data is collected, the
remainder of the buffer will be filled with post-trigger data until it is full. Actual values in the
memory map provide information as to where the true trigger position is in each log buffer.
The
TRIGGER ON <EVENT_TYPE>
waveform captures and are applicable only when the data logger is operating in trigger
mode. The
CHNL 1 SOURCE
assignable as an Analog Output parameter. See Analog Output Parameters on page 5–111
for a list of values.
If all Channel Sources (1 through 8) are set to "Disabled", then the data logger will not
collect data in continuous mode or respond to triggers in trigger mode.
PATH: SETPOINTS
S1 RELAY SETUP
[]
MESSAGE
MESSAGE
MESSAGE
These setpoints modify front panel characteristics to suit different situations.
CONTINUOUS MODE
CONTINUOUS MODE
and
setpoints are only applicable in trigger
TRIGGER POSITION
selects the number triggers stored and the samples per
setpoints select specific event types to trigger new
to
setpoints can be assigned any value
CHNL 8 SOURCE

FRONT PANEL
FLASH MSG TIME:
4.0 s
DEFAULT MSG
TIME: 300 s
DISPLAY FILTER
CONSTANT:
0
3 KEY MAX/LAST DMND
CLEARING: Disabled
S1 RELAY SETUP
to "Enabled". At each
to "Disabled". The programmed
setpoint
TRIGGER POSITION
Range: 0.5 to 10.0 s in steps
of 0.1
Range: 10 to 900 s in steps
of 1
Range: 0 to 255 in steps of 1
Range: Enabled, Disabled
5 - 17