S6 MONITORING
COIL MONITOR 1
5 - 118
The breaker does not respond to a close command within the programmed time.
When a breaker operation failure is declared, the selected output relays will operate, but
the Close Relay and 760 autoreclosure will be inhibited. If the 760 already has a reclosure
scheme in progress, it will be sent to lockout.
A Breaker Operation failure condition results if the breaker does not respond within the
time. This time is a characteristic of the breaker being used.
BRKR OPERATION DELAY
FIGURE 5–53: Breaker Operation Logic
Coil Monitor

PATH: SETPOINTS
S6 MONITORING
[]
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE


EQUIPMENT
COIL MON 1 NAME:
Trip Coil Monitor
COIL MON 1
FUNCTION: Disabled
COIL MON 1
RELAYS (3-7): -----
BREAKER STATE
BYPASS: Disabled
COIL MON 1
DELAY: 5 s
COIL MON 1
TYPE: Trip
750 FEEDER MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
COIL MONITOR 1(2)
Range: Any combination of
18 alphanumeric
Range: Disabled, Alarm,
Latched Alarm,
Control
Range: Any combination of 3
to 7 Auxiliary relays
Range: Enabled, Disabled
Range: 5 to 100 s in steps of
1
Range: Trip, Close