S7 CONTROL
RECLOSURE 1
5 - 166
Reclosure Shots 1 to 4

PATH: SETPOINTS
S7 CONTROL
[]
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The above setpoints are programmed independently and are repeated for each of the
Reclosure Shots 1 through 4. These setpoints determine the dead time for a given shot and
the overcurrent characteristics during that shot. Selections for shots, that are greater than
the maximum number of shots programmed in the scheme setup, will not be used by the
scheme.


AUTORECLOSE
DEADTIME BEFORE
RECLOSURE:
0.50 s
PHASE INST OC 1
BLOCKING: Disabled
NEUTRAL INST OC 1
BLOCKING: Disabled
GND INST OC
BLOCKING: Disabled
SENSTV GND INST OC
BLOCKING: Disabled
NEG SEQ INST OC
BLOCKING: Disabled
PHASE TIME OC 1
RAISED PICKUP: 0%
NEUTRAL TIME OC 1
RAISED PICKUP: 0%
GND TIME OC
RAISED PICKUP: 0%
SENSTV GND TIME OC
RAISED PICKUP: 0%
NEG SEQ TIME OC
RAISED PICKUP: 0%
SELECT SETPOINT
GROUP: Active
750 FEEDER MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
RECLOSURE 1(4)
Range: 0.00 to 300.00 s in
steps of 0.01
Range: Enabled, Disabled
Range: Enabled, Disabled
Range: Enabled, Disabled
Range: Enabled, Disabled
Range: Enabled, Disabled
Range: 0 to 100% in steps of
1
Range: 0 to 100% in steps of
1
Range: 0 to 100% in steps of
1
Range: 0 to 100% in steps of
1
Range: 0 to 100% in steps of
1
Range: Group 1, Group 2,
Group 3, Group 4,