P Hysical - GE 750 Instruction Manual

Hide thumbs Also See for 750:
Table of Contents

Advertisement

CHAPTER 2: INTRODUCTION
2.4.10 Physical
Note
NOTE
Note
NOTE
750 FEEDER MANAGEMENT RELAY – INSTRUCTION MANUAL
EEPROM
100000 program/erase cycles max.
CLOCK
Resolution:
Accuracy with IRIG-B:
Accuracy without IRIG-B: ±5 minutes/month
Supercap backup life:
TEMPERATURE
Operating range:
Ambient storage:
Ambient shipping:
At temperatures below –20°C, the LCD contrast may become impaired.
ENVIRONMENTAL
Ambient operating temperature:–40°C to +60°C
Ambient storage temperature:–40°C to +80°C
Humidity:
Pollution degree:
IP Rating:
LONG-TERM STORAGE
Environment:
Correct storage:
It is recommended that all relays be powered up once per year, for one hour continuously,
to avoid deterioration of electrolytic capacitors and subsequent relay failure.
CASE
Type:
Approvals:
Seal:
Door:
Mounting:
Weight:
1 ms
±1 ms
45 days when control power is off
–40°C to +60°C
–40°C to +80°C
–40°C to +80°C
up to 90% non-condensing
2
40-X
In addition to the above environmental considerations, the
relay should be stored in an environment that is dry, corrosive-
free, and not in direct sunlight.
Prevents premature component failures caused by
environmental factors such as moisture or corrosive gases.
Exposure to high humidity or corrosive environments will
prematurely degrade the electronic components in any
electronic device regardless of its use or manufacturer, unless
specific precautions, such as those mentioned in the
Environmental section above, are taken.
Fully drawout unit (automatic CT shorts)
Meets CE drawout specifications
Seal provision
Dust tight door
Panel or 19" rack mount
7.9 kg (case and relay)
9.4 kg (shipping weight)
SPECIFICATIONS
2 - 21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

760

Table of Contents