CONTROL SCHEMES
7 - 78
Check the Event Recorders in the Incomer 1 and 2 and Bus Tie relays
for the correct messages and sequences, then clear the recorders.
Low Voltage Logic
Slowly reduce test voltage Source 1 supplying Incomer relay 1.
At the pickup voltage of the Line Undervoltage 3 feature Output Relay 4
should operate.
At this time the Incomer 2 relay should display the Transfer Not Ready
message.
Slowly increase test voltage Source 1.
At the reset voltage of the Line Undervoltage 3 feature Output Relay 4
should reset.
At the Incomer 2 relay after the time delay of setpoint Transfer Delay
Other Source the message Transfer Not Ready should be removed from
the display.
Slowly reduce test voltage Source 2 supplying Incomer relay 2.
At the pickup voltage of the Line Undervoltage 3 feature Output Relay 4
should operate.
At this time the Incomer 1 relay should display the Transfer Not Ready
message.
Slowly increase test voltage Source 2.
At the reset voltage of the Line Undervoltage 3 feature Output Relay 4
should reset.
At the Incomer 1 relay after the time delay of setpoint Transfer Delay
Other Source the message Transfer Not Ready should be removed from
the display.
Turn voltages off.
Incomer breakers 1 and 2 should trip when Undervoltage 4 times out.
Check the Event Recorders in both Incomers and the Bus Tie relay for
the correct messages and sequences, then clear the recorders.
Transfer Initiated by Lockout 86-1
Energize both test sources at nominal voltage, close Incomer breakers 1
and 2, and wait until the Transfer Not Ready message is removed from
the display of both Incomer relays.
At the Incomer 1 relay assert Logic Input 12 (Transformer Lockout).
The Incomer 1 relay should trip the Incomer 1 breaker and operate
Output Relay 6 to send a Close From Incomer 1 signal to the Bus Tie
relay.
Output Relay 6 at the Incomer 1 relay should reset when the Incomer 1
breaker trips, removing the signal to the Bus Tie relay.
The Bus Tie breaker should not close as the voltage on its Bus and Line
inputs is too high.
Slowly reduce the test Source 1 voltage.
The Bus Tie breaker should close when the voltage is below the Dead
Bus Max Volts setpoint of its Synchrocheck feature.
CHAPTER 7: COMMISSIONING
750 FEEDER MANAGEMENT RELAY – INSTRUCTION MANUAL