GE 750 Instruction Manual page 232

Hide thumbs Also See for 750:
Table of Contents

Advertisement

S6 MONITORING
5.7.5
Analog Input
ANALOG INPUT
ANALOG INPUT
SETUP
5 - 106
Main Menu

PATH: SETPOINTS
S6 MONITORING
[]
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The relay can monitor any external quantity, such as transformer winding temperature,
bus voltage, battery voltage, station service voltage, transformer tap position, etc., via an
auxiliary current input called the analog input. Any one of the standard transducer output
ranges 0 to 1 mA, 0 to 5 mA, 0 to 10 mA, 0 to 20 mA, or 4 to 20 mA can be connected to the
analog input terminals.
Two independent elements are available for monitoring the analog input level, Analog
Threshold 1 and 2, each having a user programmable name, pickup level, drop out ratio,
and a time delay. For each element, when the measured analog input quantity exceeds
the pickup level for longer than the associated time delay, the relay can be configured to
cause a trip, an alarm, or signal an output contact. The element will drop out only when the
user programmed drop out ratio has been met. There are also two elements which
measure the analog input rate-of-change, Analog In Rate 1 and 2, which operate in a
similar fashion.
Analog Input Setup

PATH: SETPOINTS
S6 MONITORING
[]
MESSAGE
MESSAGE
MESSAGE
MESSAGE

ANALOG INPUT
ANALOG INPUT
SETUP
ANALOG
THRESHOLD 1
ANALOG
THRESHOLD 2
ANALOG INPUT
RATE 1
ANALOG INPUT
RATE 2

ANALOG INPUT
A/I NAME:
ANALOG INPUT
A/I UNITS:
μ
A
A/I RANGE:
0-20 mA
A/I MIN
μ
VALUE:
0
A
A/I MAX
μ
VALUE: 20000
A
750 FEEDER MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
[]
See page 5–106
[]
See page 5–107
[]
See page 5–107
[]
See page 5–109
[]
See page 5–109
ANALOG INPUT SETUP
Range: Any combination of
20 alphanumeric
Range: Any combination of 6
alphanumeric
Range: 0-1 mA, 0-5 mA, 4-20
mA, 0-20 mA, 0-10
Range: 0 to 65535 units in
steps of 1.
Range: 0 to 65535 units in
steps of 1.