CHAPTER 6: ACTUAL VALUES
6.2.3
Last Trip Data
LAST TRIP DATA
750 FEEDER MANAGEMENT RELAY – INSTRUCTION MANUAL
PATH: ACTUAL VALUES
A1 STATUS
[]
DATE OF LAST TRIP:
Nov 17 2003
TIME OF LAST TRIP:
MESSAGE
12:34:56.789
TRIP: <Φ>
MESSAGE
<Cause>
A:
MESSAGE
C:
GND CURRENT:
MESSAGE
SENSTV GND CURRENT:
MESSAGE
0.00 A
NEUTRAL CURRENT:
MESSAGE
AN:
MESSAGE
CN:
AB:
MESSAGE
CA:
NEUTRAL VOLTAGE:
MESSAGE
0.00 kV
SYSTEM FREQ:
MESSAGE
0.00 Hz
ANALOG INPUT:
MESSAGE
Independent of the event recorder, the relay captures the system information at the time of
the last trip event. This information includes a time and date stamp, trip cause, phase
current, ground current, sensitive ground current, neutral current, voltages, system
frequency, and the analog input. If more than one protection element trips for a fault (for
example, both the Phase and Neutral Instantaneous Overcurrent 1 elements) then only the
first trip event detected by the relay will have Last Trip Data captured. This information
cannot be cleared; data for a new trip overwrites the previous trip data.
The AN, BN, and CN voltage values are seen only if the
SENSING
VT CONNECTION TYPE
seen only if this setpoint is "Delta" or "None". The units for

MONITORING
ANALOG INPUT

LAST TRIP DATA
0
B:
0
0
Amps
0 A
0 A
0.00
BN:
0.00
0.00
kVolts
0.00
BC:
0.00
0.00
kVolts
0 μA
setting is "Wye". The AB, BC, and CA voltage values are

ANALOG INPUT SETUP
A1 STATUS
Range: Date in format shown
Range: Time in format shown
Range: See A4 Event Recorder on page
6–20.
Range: 0 to 65535 A
Range: 0 to 65535 A
Range: 0 to 655.35 A
Range: 0 to 65535 A
Range: 0 to 655.35 kV
Range: 0 to 655.35 kV
Range: 0 to 655.35 kV
Range: 0.00 to 65.00 Hz
Range: 0 to 65535 units.

S2 SYSTEM SETUP
are set by the
ANALOG INPUT
setting.

A/I UNITS
BUS VT
S6
6 - 7

Hide quick links:

Advertisement

Table of Contents
loading