CHAPTER 5: SETPOINTS
RATE
SUPERVISION
750 FEEDER MANAGEMENT RELAY – INSTRUCTION MANUAL
Autoreclose Rate Supervision
PATH: SETPOINTS
S7 CONTROL
[]
MESSAGE
MESSAGE
The autoreclose rate supervision feature monitors the number of reclosures per hour. Once
the number of reclosures within one hour exceeds the
the autoreclose scheme is sent to lockout.
FIGURE 5–77: Autoreclose Rate Supervision Logic
AUTORECLOSE
RATE SUPERVISION
FUNCTION: Disabled
RATE SUPERVISION
RELAYS (3-7): -----
MAX AUTORECLOSE
RATE: 25 /hr.
MAX AUTORECLOSE RATE
S7 CONTROL
RATE SUPERVISION
Range: Disabled, Alarm,
Latched Alarm,
Range: Any combination of
the 3 to 7 Auxiliary
Range: 1 to 50/hr. in steps of
1
setpoint,
5 - 161