MECHANICAL INSTALLATION
3.1.2
Installation
3 - 2
entry of setpoints and still allow monitoring of actual values, access to the front panel
controls may still need to be restricted. As such, a separate seal can be installed on the
outside of the door to prevent it from being opened.
The 750/760 can be mounted alone or adjacent to another SR-series unit on a standard
19-inch rack panel. Panel cutout dimensions for both conditions shown below. When
planning the location of your panel cutout, ensure provision is made for the front door to
swing open without interference to or from adjacent equipment.
FIGURE 3–3: Single and Double Unit Panel Cutouts
Before mounting the relay in the supporting panel, remove the unit from the case. From the
front of the panel, slide the empty case into the cutout. To ensure the front bezel is flush
with the panel, apply pressure to the bezel's front while bending the retaining tabs 90°.
These tabs are located on the sides and bottom of the case and appear as shown in the
illustration. After bending all tabs, the case will be securely mounted so that its relay can be
inserted. The unit is now ready for panel wiring.
FIGURE 3–2: Drawout Case Seal
750 FEEDER MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
DRAWOUT
CASE SEAL