CHAPTER 7: COMMISSIONING
7.3.5
Analog Input
Metering
750 FEEDER MANAGEMENT RELAY – INSTRUCTION MANUAL
Reactive Power Demand
For these tests, refer to the figures in section 7.1.6 for test connections. The expected
accuracy is as follows:
Expected Accuracy: ±2.0% of full scale
The relevant actual values displays are shown below:
A2 METERING
A2 METERING
A2 METERING
A2 METERING
 Follow the procedure in Current Demand on page 7–21, except that the
injected and monitored parameter is vars.
Apparent Power Demand
For these tests, refer to the figures in section 7.1.6 for test connections. The expected
accuracy is as follows:
Expected Accuracy: ±2.0% of full scale
The relevant actual values displays are shown below:
A2 METERING
A2 METERING
A2 METERING
A2 METERING
Follow the procedure in Current Demand on page 7–21, except that the injected and
monitored parameter is VA.
For these tests, refer to the figures on page –4 for test connections. The expected accuracy
is as follows:
Expected Accuracy: ±1.0% of full scale
The relevant actual values displays are shown below:
A2 METERING
A2 METERING
A2 METERING
The procedure for testing the Analog Input metering is shown below:
 Inject steady values of DC current (in mA) of various values into relay
terminals A1(+) and A2(–).
 Verify that the analog input is correctly measured and displayed in the
value.
I
 Inject a fixed rate of ramping DC current (in mA) of various values into
relay terminals A1(+) and A2(–) for at least 2 minutes.
 At the end of this time, verify that the analog input is correctly measured
and displayed in the
 Inject a fixed rate of ramping DC current (in mA) of various values into
relay terminals A1(+) and A2(–) for at least 2 hours.
DMND
REACTIVE PWR
DMND
REACTIVE PWR
DMND
REACTIVE PWR
DMND
REACTIVE PWR
DMND
APPARENT PWR
DMND
APPARENT PWR
DMND
APPARENT PWR
DMND
APPARENT PWR
A/I
A/I
A/I
A/I (/MIN)
A/I
A/I (/HOUR)
value.
A/I (/MIN)
METERING
LAST REACTIVE PWR DMND
MAX REACTIVE PWR DMND
MAX REACTIVE PWR DATE
MAX REACTIVE PWR TIME
LAST APPARENT PWR DMND
MAX APPARENT PWR DMND
MAX APPARENT PWR DATE
MAX APPARENT PWR TIME
A/
7 - 23