S6 MONITORING
5.7.8
Equipment
EQUIPMENT
TRIP COUNTER
5 - 114
Main Menu

PATH: SETPOINTS
S6 MONITORING
[]
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The equipment monitoring features are provided to detect failures or unusual operating
conditions of the feeder circuit breaker and the bus VTs.
Trip Counter

PATH: SETPOINTS
S6 MONITORING
[]
MESSAGE
MESSAGE
When the total number of
setpoint, an output will occur. The
MAINTENANCE
TRIP COUNTERS

EQUIPMENT
TRIP COUNTER
ARCING CURRENT
BREAKER
OPERATION
COIL MONITOR 1
COIL MONITOR 2
VT FAILURE

EQUIPMENT
TRIP COUNTER
FUNCTION: Disabled
TRIP COUNTER
RELAYS (3-7): -----
TRIP COUNTER
LIMIT: 10000 Trips
detected reaches the
BREAKER TRIPS
value can be viewed in the
BREAKER TRIPS
menu.
750 FEEDER MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
[]
See page 5–114
[]
See page 5–115
[]
See page 5–117
[]
See page 5–118
[]
See page 5–118
[]
See page 5–119
TRIP COUNTER
Range: Disabled, Alarm,
Latched Alarm,
Range: Any combination of 3
to 7 Auxiliary relays
Range: 1 to 10000 Trips in
steps of 1
TRIP COUNTER LIMIT
A3