5.3.5

Current Expert Mode

For a single-phase connection, this mode displays the Current expert mode.
1
ITEM
FUNCTION
1.
This information concerns the following elements:
-: "negative" sequence.
0: "zero" sequence.
+: "positive" sequence.
%: Sums of the levels of "voltage" harmonics classified by sequence ("negative" to
the left, "zero" in the centre, and "positive" to the right). See NOTE.
2.
Sequences of current harmonics*
*Not available with a balanced three-phase connection.
NOTE: The effects of the sequences are the following:
"Negative" sequence
Overheating of rotating machine.
Loss of torque.
Mechanical oscillations.
Higher current draw for a given load.
Premature ageing of rotating machine.
"Zero" sequence
Overheating of rotating machine.
Higher current draw for a given load.
Overload of the neutral.
Premature ageing of rotating machine.