Press the Enter
Use the ◄ and ► buttons to change a value or setting.
When finished, return to the Configuration menu by pressing the
PARAMETER
Date / Time
Contrast / Brightness
Colors
Calculation Method
Electrical Hookup
Current Sensors
Recording
Alarms
Clear Memory
About
Power Quality Analyzer Model 8230
button to select a parameter.
FUNCTION
Sets the date and time format
Adjusts the contrast and brightness of the display
Defines the color of the voltage and current curves
Determines if harmonics are used or not used in calculations of
reactive quantities (power and energy)
Determines the type of connection to the network:
Single-phase: measurement of phase-to-earth voltage associated
with the phase-to-earth current of a phase.
Balanced three-phase: measurement of the complementary
phase-to-phase voltage of the phase of which the phase-to-earth
current is measured. The connection is used to calculate:
• The total powers and energies of a balanced three-phase
network (W, Wh, VAR, VARh, VA and VAh).
• The quantities common to the three phases (phase shift of
the phase-to-earth voltage with respect to the phase-to-earth
current, PF, DPF and tangent).
Defines the type of current sensor to connect
• MN93: 200A
• MN193: 100A or 5A
• SR193: 1000A
• AmpFlex
Sensors: 3000A
®
• MiniFlex
Sensors: 1000A
®
• MR193: 1000A
• 5A three-phase adapter (one phase only)
Selects the parameters of a recording (see § 4.1.2)
Defines the parameters of an alarm (see § 4.1.3)
Deletes all data (configurations, alarm settings, snapshots and
recordings). The configuration will return to the default setting.
Displays the serial number, software and hardware version.
button.
21