Hysteresis

Hysteresis is a filtering principle, often used after the threshold detection has
occurred. A correct setting of hysteresis value will avoid repeated triggering when
the measure is varying close to the threshold.
The event detection is activated when the measure is going over the threshold but
it can only be deactivated if the measure goes under the threshold minus the value
of the hysteresis.
The default hysteresis value is 2% of the reference voltage but it may be set in the
range of [1%, 5%] depending of the voltage stability on the system.
Detection of voltage overload
Hysteresis =
2% Uref
Undervoltage or blackout detection
Hysteresis =
2% Uref
82
Swell duration
Duration
Power Quality Analyzer Model 8230
Threshold of swell =
100% Uref
Level to go back =
100% - 2% = 98% Uref
Level to go back =
(100% + 2%)Uref
Threshold = 102% Uref