Four recording set-ups are available. Choose recording CONFIG 1, 2, 3, or 4
by pressing enter, then use the ▲ button to select the desired configuration
number. Press enter again to validate the selection.
Next, move through the choices with the ◄ and ► buttons and select the
desired parameters with the ▲ and ▼ buttons. As you move through the
parameters, each choice, in turn, will be highlighted.
To activate the highlighted parameter for recording, press the Enter
The selected parameters will have a filled in and those not selected will have
an unfilled .
There are two user-defined parameters at the bottom of the window. At first,
they will be listed as a question mark "?". These parameters allow you to
monitor specific, or a range, of voltage, current or power harmonics.
To activate the user-defined parameters:
-
Select the parameter with the ◄ ► buttons, press the Enter button and
choose a value (VAh, Ah or Vh). Press Enter again to validate.
-
Once the desired parameter is selected, use the ► button to select the
desired harmonic order. A value from 00 to 50 may be selected for this
field using the ▲ and ▼ buttons.
-
After selecting the desired harmonic order for the beginning value, press
the ► button to move to the upper value. Use the same process to select
the upper limit.
-
Press the ► button again to move to the right to modify the last value
needed to complete the definition. Here you will choose whether to in-
clude all harmonics or only the odd harmonics.
-
Use the ▲ and ▼ buttons to make this selection. The diamond preced-
ing the Odd Only choice will appear filled in
for not selected.
Example of a user defined choice: Vh 02 → 15
In this user defined condition, all odd voltage harmonics between the 2nd and the 15th
will be recorded.
Press the enter button when you have finished selecting all the parameters to
be recorded to apply the new setup.
WARNING: The battery may fully discharge when recording for long periods
of time if not connected to a power supply. The PowerPad
record for some time, even if below the minimum battery charge value. However,
the display may not come back on, and will eventually stop saving data when the
battery is too low. All data recorded will be saved.
If in the Record Mode, and the display does not come ON, do not turn the instru-
ment OFF. Supply power to the PowerPad
will come back ON when any button (other than ON/OFF) is pressed.