7 Settings
Parameter
Factory setting for each circuit
Zone HCZP
CIRCA1: 15
Reduced
CIRCB1: 15
(CP220
DHW1: 15
CP221
CIRCC1: 15
CP222
CIRCAUX1: 15
CP223
CP224)
TypeReducedNig
CIRCA1: Stop heat demand
htMode
CIRCB1: Stop heat demand
(CP340
DHW1: Stop heat demand
CP341
CIRCC1: Stop heat demand
CP342
CIRCAUX1: Stop heat demand
CP343
CP344)
Control strategy
CIRCA1: Automatic
(CP780
CIRCB1: Automatic
CP781
DHW1: not used
CP782
CIRCC1: Automatic
CP783
CIRCAUX1: Automatic
CP784)
Tab.79
Adv. Parameters menu
Parameter
Factory setting for each circuit
ConfigZonePump
CIRCA1: Zone output
Out
CIRCB1: Zone output
(CP290
DHW1: DHW mode
CP291
CIRCC1: Zone output
CP292
CIRCAUX1: DHW looping
CP293
CP294 )
Zone Buffered
CIRCA1: Yes
(CP770
CIRCB1: Yes
CP771
DHW1: Yes
CP772
CIRCC1: Yes
CP773
CIRCAUX1: Yes
CP774 )
Tab.80
Parameters menu
Parameter
Description
DhwMaxTemp
Max. flow temperature for domestic hot water production.
(DP046)
Can be set from 10 to 70 °C
Max. DHW duration
Maximum authorised duration for domestic hot water production.
(DP047)
Can be set from 1 to 10 hours
Min. CH before DHW
Minimum heating duration between two domestic hot water production runs.
(DP048)
Can be set from 0 to 10 hours
66
MIT-M
Description
Reduced footpoint of the temperature of heat curve of the circuit
can be set from 6 to 90 °C
set to 15 = the curve base temperature is set automatically and is
the same as the room set point temperature
Type of reduced night mode, stop or maintain heating of circuit
Stop heat demand
Continue heat demand
Selection of the control strategy for the zone
Automatic
Room Temp. based
Outdoor Temp. based
Outdoor & room based
Description
Configuration of Zone Pump Output
Zone output
CH mode
DHW mode
Cooling mode
Error report
Burning
Service flag
System error
DHW looping
Primary pump
Buffer pump
The zone is after a Buffer tank
No
Yes
7.4.3
Installation Setup > Stratified DHW tank > Parameters,
counters, signals
A domestic hot water sensor must be connected to the EHC–05 PCB to
display these parameters. The Stratified DHW tank circuit is on the EHC–
05 PCB.
Factory setting
70 °C
3 hours
2 hours
7756241 - v02 - 19062020