DVC6200f Digital Valve Controller
the LOOP screw terminals on the pwb/terminal strip
assembly in the terminal box shown in figure 2-8.
Connect the other wire from the control system output
card to the other LOOP screw terminal in the terminal
box.
2
Personal injury or property damage
can result from the discharge of static
electricity. Connect a 14 AWG (2.08
2
mm
) ground strap between the
digital valve controller and earth
ground when flammable or hazardous
gases are present. Refer to national
and local codes and standards for
grounding requirements.
4. As shown in figure 2-8, two ground terminals are
available for connecting a safety ground, earth ground,
or drain wire. The safety ground terminal is electrically
identical to the earth ground. Make connections to
these terminals following national and local codes and
plant standards.
To avoid static discharge from the
plastic cover, do not rub or clean the
cover with solvents. Clean with a mild
detergent and water only.
5. Replace and hand tighten the cover on the terminal
box. When the loop is ready for startup, apply power
to the control system output card.
Making Fieldbus Connections with the
Quick Connect Cable Entry
The DVC6200f is offered with a quick connect cable
entry option, shown in figure 2-9, for the
fieldbus signal. The quick connect cable entry provides
an easier and more reliable interface to fieldbus
devices and support modules by providing a standard
connection.
20
WARNING
WARNING
F
OUNDATION
1/2-14 NPT
NOTES:
1. COLORS ARE WIRE COLORS.
2. NC=NO CONNECTION.
18B9424-A
Figure 2-9. Quick Connect Connector
Note
The quick connect cable entry option
is only available for intrinsically safe
and non-incendive installations.
Refer to figure 8-2 for identification of parts.
WARNING
Personal injury or property damage,
caused by fire or explosion, can result
from the discharge of static electricity.
Connect a 14 AWG (2.08 mm
strap between the digital valve
controller and earth ground when
flammable or hazardous gases are
present. Refer to national and local
codes and standards for grounding
requirements.
To avoid static discharge from the
plastic cover, do not rub or clean the
cover with solvents. Clean with a mild
detergent and water only.
To avoid personal injury or property
damage, do not use the Quick
Connect option on instruments in
explosion-proof or flameproof
installations.
1. The quick connect cable entry should be installed
on the digital valve controller at the factory. If it is,
proceed to step 3. If not continue with step 2.
2. To install the Quick Connect:
a. Remove the terminal box cap (key 4) from the
terminal box (key 3).
1
3
(BLUE)
(NC)
4
2
(GREEN/YELLOW)
(BROWN)
2
) ground
November 2010